Plan Review Notes For Permit 16080290 |
Permit Number |
16080290 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-15 15:57:52 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16080290 | | 8/15/16 | | | | 1) THE PLAN IS NOT IN COMPLIANCE WITH TABLE 403.3 AND | | FOOTNOTES B AND H. THE 4 NAIL STATIONS SHOWN REQUIRE 50 | | CFMS OF EXHAUST EACH, AND EACH NAIL STATION IS REQUIRED | | TO HAVE A SOURCE CAPTURE SYSTEM. THE BEAUTY SALON SPACE | | IN TOTAL IS REQUIRED TO HAVE AN EXHAUST VENTILATION | | SYSTEM DESIGNED AT 0.6 CFMS PER SQ. FT. PLEASE REVISE | | THE PLANS AND CALCULATIONS TO SHOW COMPLIANCE. | | PLEASE NOTE THAT O/A FOR THE SALON SHALL BE PROVIDED AT | | A RATE 20 CFMS PER PERSON AND 0.12 CFMS PER SQ. FT. OF | | SPACE. | | | | 2) PROVIDE AIR BALANCE CALCULATIONS- REFER TO SECTION | | 501.4 | | | | 3) PROVIDE BOTH A REFLECTIVE CEILING PLAN, AND AN AC | | LAYOUT PLAN SHOWING THE LOCATIONS OF ALL SUPPLY AND | | RETURN DIFFUSERS AND GRILLS. THERE IS AN AIR DEVICE | | SCHEDULE ON M-1 BUT NO DETAILS ON THE PLAN. | | | | 4) INDICATE THE TYPES AND SIZES OF THE NEW EXHAUST | | DUCTS, AND VERIFY COMPLIANCE WITH SECTION 501.3.1 FOR | | OUTLET TERMINATION LOCATION, AND 501.3.2 FOR OPENING | | PROTECTION. | | | | 5) INDICATE HOW THE EXHAUST FANS WILL ACTIVATE. THE | | ELECTRICAL PLANS TO DO NOT INDICATE SWITCHES OR OTHER | | METHODS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|