Plan Review Notes
Plan Review Notes For Permit 16080290
Permit Number 16080290
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-08-10 12:18:59321 SOUTH DIXIE HIGHWAY
 PERMIT #16080290
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A2: WATER HEATER DOES NOT APPEAR TO BE FIRE
 SEPARATED FROM THE EXISTING STAIR. PER NFPA 101 SECTION
 7.2.2.5.3.2, ENCLOSED, USABLE SPACE SHALL BE PERMITTED
 UNDER STAIRS, PROVIDED THAT THE SPACE SHALL BE
 SEPARATED FROM THE STAIR ENCLOSURE BY THE SAME FIRE
 RESISTANCE AS THE EXIT ENCLOSURE.
  
 SHEET A2: LAUNDRY DOOR SWING OBSTRUCTS EGRESS. PER NFPA
 101 SECTION 7.2.1.4.3.1, DURING ITS SWING, ANY DOOR IN
 A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF
 THE REQUIRED WIDTH OF AN AISLE, CORRIDOR, HALLWAY OR
 LANDING UNOBSTRUCTED AND SHALL PROJECT NOT MORE THAN
 7-INCHES INTO THE REQUIRED WIDTH OF THE EGRESS PATH
 WHEN FULLY OPEN.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE