2016-08-12 10:43:26 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: FUSION HAIR SALON |
| JOB ADDRESS: 321 S. DIXIE HWY. |
| DESCRIPTION: INTERIOR IMPROVEMENT ? NEW HAIR SALON |
| MASTER PERMIT: 16080290 |
| |
| BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL |
| REVIEW: |
| |
| 1. NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED |
| BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE |
| LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON |
| OWN CIRCUIT, OTHERWISE THEY SHALL BE ON THE SAME |
| CIRCUIT AS FOR THE LIGHTING OF THE ROOM THEY OCCUPY. |
| 2. NEC 600.5 - EACH COMMERCIAL BUILDING AND EACH |
| COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS SHALL BE |
| PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED OUTLET IN |
| AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT |
| SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE HALLWAYS OR |
| CORRIDORS SHALL NOT BE CONSIDERED ACCESSIBLE TO |
| PEDESTRIANS. THE SUBMITTED DRAWING DOES NOT INDICATE |
| THIS ON THE PANEL SCHEDULE OR THE FLOOR PLAN. |
| 3. NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE |
| OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A |
| SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR PORTION |
| THEREOF AREA MEASURED HORIZONTALLY. THE SUBMITTED |
| DRAWING DOES NOT INDICATE THIS ON THE PANEL SCHEDULE OR |
| THE FLOOR PLAN. |
| 4. NEC 422.31. PERMANENTLY CONNECTED APPLIANCE OF OVER |
| 300 VA OR 1/8 HP REQUIRES A DISCONNECT WITHIN SIGHT OF |
| THE APPLIANCE. MARK ON THE PLANS THE DISCONNECT FOR THE |
| WATER HEATER. |
| 5. NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL |
| EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO |
| REQUIRE SERVICE WHILE ENERGIZED SHALL BE FIELD MARKED |
| TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS. THIS CAN |
| BE ADDRESSED WITH A BLOCK NOTE ON THE PLANS. |
| 6. NEC 110.24 THE MAXIMUM AVAILABLE FAULT CURRENT SHALL |
| BE DURABLY MARKED AND DATED ON ALL NON-DWELLING |
| ELECTRICAL APPARATUS. THIS CAN BE ADDRESSED WITH A |
| BLOCK NOTE ON THE PLANS. |
| 7. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT |
| SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY. |
| 8. FBC-E SECTION C405 REQUIRES MANDATORY LIGHTING |
| CONTROL. |
| 9. FBC-EC 405.2.2.2 REQUIRES OCCUPANCY SENSORS IN THE |
| RESTROOMS, STORAGE CLOSET, PRIVATE OFFICES AND SIMILAR |
| ROOMS. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |