Plan Review Notes
Plan Review Notes For Permit 16080290
Permit Number 16080290
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-12 10:43:26ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: FUSION HAIR SALON
 JOB ADDRESS: 321 S. DIXIE HWY.
 DESCRIPTION: INTERIOR IMPROVEMENT ? NEW HAIR SALON
 MASTER PERMIT: 16080290
  
 BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL
 REVIEW:
  
 1. NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED
 BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE
 LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON
 OWN CIRCUIT, OTHERWISE THEY SHALL BE ON THE SAME
 CIRCUIT AS FOR THE LIGHTING OF THE ROOM THEY OCCUPY.
 2. NEC 600.5 - EACH COMMERCIAL BUILDING AND EACH
 COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS SHALL BE
 PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED OUTLET IN
 AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE HALLWAYS OR
 CORRIDORS SHALL NOT BE CONSIDERED ACCESSIBLE TO
 PEDESTRIANS. THE SUBMITTED DRAWING DOES NOT INDICATE
 THIS ON THE PANEL SCHEDULE OR THE FLOOR PLAN.
 3. NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR PORTION
 THEREOF AREA MEASURED HORIZONTALLY. THE SUBMITTED
 DRAWING DOES NOT INDICATE THIS ON THE PANEL SCHEDULE OR
 THE FLOOR PLAN.
 4. NEC 422.31. PERMANENTLY CONNECTED APPLIANCE OF OVER
 300 VA OR 1/8 HP REQUIRES A DISCONNECT WITHIN SIGHT OF
 THE APPLIANCE. MARK ON THE PLANS THE DISCONNECT FOR THE
 WATER HEATER.
 5. NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL
 EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO
 REQUIRE SERVICE WHILE ENERGIZED SHALL BE FIELD MARKED
 TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS. THIS CAN
 BE ADDRESSED WITH A BLOCK NOTE ON THE PLANS.
 6. NEC 110.24 THE MAXIMUM AVAILABLE FAULT CURRENT SHALL
 BE DURABLY MARKED AND DATED ON ALL NON-DWELLING
 ELECTRICAL APPARATUS. THIS CAN BE ADDRESSED WITH A
 BLOCK NOTE ON THE PLANS.
 7. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT
 SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY.
 8. FBC-E SECTION C405 REQUIRES MANDATORY LIGHTING
 CONTROL.
 9. FBC-EC 405.2.2.2 REQUIRES OCCUPANCY SENSORS IN THE
 RESTROOMS, STORAGE CLOSET, PRIVATE OFFICES AND SIMILAR
 ROOMS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  