2016-08-13 10:57:32 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16080290 |
| ADD: 321 S. DIXIE HWY. |
| CONT: MASTER CONTRACTOR |
| TEL: 561-248-5498 |
| E-MAIL: MASTERCONTRACTORS@?????????? |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SAT. AUGUST 13/ 2016 |
| ACTION: DENIED |
| |
| 1) THE COVERSHEET INDICATES THIS 2 STORY BUILDING IS A |
| BUILDING TYPE IIA-SPRINKLERED. PLEASE NOTE THIS 2 STORY |
| BUILDING WAS BUILT IN 1925 THE 1ST FLOOR CONSISTING OF |
| EITHER BUSINESS AND OR MERCANTILE. THIS BUILDING TYPE |
| IS NOT A TYPE IIA BUILDING, MORE LIKELY A TYPE VB. A |
| TYPE IIA MEANS THERE IS NO WOOD IN THE STRUCTURE AND |
| ALL OF THE STRUCTURAL MEMBERS ARE 1 HOUR FIRE PROTECTED |
| PER TABLE 601. |
| |
| 2) THE COVERSHEET ALSO LIST THE OCCUPANCY TYPE AS |
| BUSINESS/ RETAIL, THE TENANCY SQUARE FOOTAGE OF 827 AND |
| AN OCCUPANT LOAD OF 13. PLEASE PROVIDE THE SQUARE |
| FOOTAGE FOR THE BEAUTY SALOON PORTION THAT WILL BE |
| BUSINESS OCCUPANCY AND THE POTION THAT WILL BE |
| MERCANTILE OCCUPANCY. THIS TENANCY MAY BE CLASSIFIED AS |
| A MIXED USE OCCUPANCY. |
| 2014 FBC-B 508.2.1 AREA LIMITATIONS. AGGREGATE |
| ACCESSORY OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10 |
| PERCENT OF THE BUILDING AREA OF THE STORY (TENANT |
| SPACE) IN WHICH THEY ARE LOCATED AND SHALL NOT EXCEED |
| THE TABULAR VALUES IN TABLE 503, WITHOUT BUILDING AREA |
| INCREASES IN ACCORDANCE WITH SECTION 506 FOR SUCH |
| ACCESSORY OCCUPANCIES. |
| |
| 3) THE COVERSHEET LIST 13 OCCUPANTS BUT THE FLOOR PLAN |
| INDICATES IF EACH CHAIR IS TAKEN BY AN OCCUPANT AND |
| BEAUTICIAN AT EACH STATION THE OCCUPANT LOAD WOULD BE |
| CLOSER TO 30 OCCUPANTS. |
| 2014 FBC-B 1004.2 INCREASED OCCUPANT LOAD. THE OCCUPANT |
| LOAD PERMITTED IN ANY BUILDING, OR PORTION THEREOF, IS |
| PERMITTED TO BE INCREASED FROM THAT NUMBER ESTABLISHED |
| FOR THE OCCUPANCIES IN TABLE 1004.1.2, PROVIDED THAT |
| ALL OTHER REQUIREMENTS OF THE CODE ARE ALSO MET BASED |
| ON SUCH MODIFIED NUMBER AND THE OCCUPANT LOAD DOES NOT |
| EXCEED ONE OCCUPANT PER 7 SQUARE FEET (0.65 M2) OF |
| OCCUPIABLE FLOOR SPACE. |
| |
| 4) SHEET A-1. THE DOOR SWING OF THE LAUNDRY ROOM DOOR |
| SWINGS OVER ? OF THE REQUIRED EGRESS PATH. 1005.7.1 |
| DOORS. |
| DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED |
| WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY |
| POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE |
| THAN ONE-HALF. |
| |
| 5) SHEET A-1. PLEASE NOTE THERE IS AN EXISTING STAIR TO |
| A TENANCY ABOVE THIS UNIT. THE PLANS INDICATE AN |
| EXISTING WATER HEATER BELOW THE STAIR ENCLOSURE. PLEASE |
| PROVIDE COMPLIANCE WITH 2014 FBC-B 1009.9.3 ENCLOSURES |
| UNDER INTERIOR STAIRWAYS. |
| THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE SPACES |
| UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE |
| PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION |
| OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY |
| ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED |
| SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR |
| ENCLOSURE. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |