2016-08-15 07:53:321ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #16080247
 8/15/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR. PLEASE NOTE THAT LOCKER
 ROOMS REQUIRE EXHAUST AT A RATE OF 0.5 CFM'S PER SQ.
 FT. AND RECIRCULATION OF AIR IS LIMITED TO 10% OF THE
 SUPPLY AIR STREAM.
  
 2) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS
 THAT INDICATES WHICH AREAS OF THE OCCUPANCY ARE BEING
 CONDITIONED BY THE NEW AC SYSTEMS.
  
 3) SHEET M-1.1: SHOW THE LOCATIONS OF THE EXISTING
 AHU'S AND SUPPLY, RETURN, AND O/A DUCTWORK. HOW CAN THE
 O/A BRANCH DUCTS TO THE NEW UNITS BE EXISTING? PLEASE
 INDICATE THE SIZES OF THE EXISTING AND NEW O/A DUCTS.
  
 4) M-1.1: PROVIDE COMPLETE SUPPLY AND RETURN DUCTWORK
 PLANS FOR THE NEW AHU'S. HOW IS AIR BEING RETURNED TO
 THE UNITS FROM ALL THE ROOMS AND SPACES?
  
 5) M-1.1: A NEW MECHANICAL CLOSET IS BEING CREATED FOR
 AHU-1. PLEASE NOTE THAT ALL MATERIALS IN THE CLOSET
 INCLUDING THE NEW DOOR SHALL BE NON-COMBUSTIBLE OR
 PLENUM-RATED- SEE SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION.
  