Plan Review Notes
Plan Review Notes For Permit 16080247
Permit Number 16080247
Review Stop B
Sequence Number 1
Notes
Date Text
2016-08-13 07:57:48BUILDING PLAN REVIEW
 W. P. B. REVISION: 16080247
 W. P. B. PERMIT: 16020859
 ADD: 8055 IRONHORSE BLVD./ CLUBHOUSE
 CONT: CUTTING EDGE BUILDING SYSTEMS
 TEL: 561-282-8265
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. AUGUST 13/2016
 ACTION: DENIED
  
 1) SHEET A2.0 SHOWS IN THE MENS/ WOMENS ATTEDANT ROOM
 THE AIR HANDLER BEING RELOCATED WITHIN A NEW CLOSET
 WITH DOUBLE DOORS IN FRONT FOR ACCESS AND A DOOR ON ONE
 SIDE FOR ACCESS. SHEET ALR4.1 DOES NOT SHOW A RETURN
 DUCT, IT WOULD APPEAR THE CLOSET IS TO BE CONSIDERED A
 PLENUM. THE PLANS GIVE NO INFORMATION ON THE WALL
 FINISHES NOR THE TYPE OF MATERIALS THE DOORS ARE MADE.
 2014 FBC-M 602.2.1 MATERIALS WITHIN PLENUMS. EXCEPT AS
 REQUIRED BY SECTIONS 602.2.1.1 THROUGH 602.2.1.5,
 MATERIALS WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR
 SHALL BE LISTED AND LABELED AS HAVING A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM
 E 84 OR UL 723. PLEASE PROVIDE WALL FINSIHES OF THE AIR
 HANDLER CLOSET AND OF THE DOORS.
  
 2) SHEET A2.0 & ALF4.1 THE MENS/ WOMENS ATTENDANT
 ACCESS ROOM DOOR NOT IDENTIFIED ALSO HAS A NEW
 STRUCTURE AROUND IT. THIS DOOR NO LONGER HAS THE
 REQUIRED MANEUVERING CLEARANCES AROUND IT BY THE 2014
 FBC-ACCESS. CODE. 404.2.4.1 18 INCHES ON THE PULL SIDE
 OF THE DOOR LATCH SIDE.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  