2016-08-15 10:59:50 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| 1) FACE SHEET FOR HYDRAULIC CALCULATIONS BLDG. "C" |
| NORTH - PAGE 1 0F 1 INDICATES AN AREA OF 3000FT2; |
| HOWEVER, THE HYDRAULIC OVERVIEW SHEET AND PLAN SHEET |
| INDICATES 2000FT2. |
| |
| PLEASE PROVIDE A REVISION FOR CORRECTION. |
| |
| |
| 2) THE FIRST SHEET INDICATES A SCALE OF 1" TO 500' |
| APPEARS TO BE INACCURATE. |
| |
| PLEASE PROVIDE A REVISION FOR CORRECTION. |
| |
| |
| 3) THE PLAN SHEETS ARE NOT NUMBERED OR IDENTIFIED. I |
| HAVE INSERTED TEMPORARY NUMBERS I.E. 1 OF 8, ETC. |
| |
| PLEASE PROIVDE A REVISION FOR CORRECTION. |
| |
| |
| 4) THE SECOND SHEETS PUMP SECTION VIEWS DO NOT CLEARLY |
| INDICATE THE MINIMUM DISTANCE FROM THE SUCTION TO THE |
| ELBOW. |
| |
| 4.14.6.3 ELBOWS AND TEES. |
| 4.14.6.3.1 UNLESS THE REQUIREMENTS OF 4.14.6.3.2 ARE |
| MET, ELBOWS AND TEES WITH A CENTERLINE PLANE PARALLEL |
| TO A HORIZONTAL SPLIT-CASE PUMP SHAFT SHALL NOT BE |
| PERMITTED. (SEE FIGURE A.4.14.6.) |
| 4.14.6.3.2 THE REQUIREMENTS OF 4.14.6.3.1 SHALL NOT |
| APPLY TO ELBOWS AND TEES WITH A CENTERLINE PLANE |
| PARALLEL TO A HORIZONTAL SPLIT-CASE PUMP SHAFT WHERE |
| THE DISTANCE BETWEEN THE FLANGES OF THE PUMP SUCTION |
| INTAKE AND THE ELBOW AND TEE IS GREATER THAN 10 TIMES |
| THE SUCTION PIPE DIAMETER. |
| 4.14.6.3.3 ELBOWS WITH A CENTERLINE PLANE PERPENDICULAR |
| TO THE HORIZONTAL SPLIT-CASE PUMP SHAFT SHALL BE |
| PERMITTED AT ANY LOCATION IN THE PUMP SUCTION INTAKE. |
| |
| PLEASE PROVIDE JUSTIFICATION OR CLEARLY INDICATE ON |
| REVISION THE COMPLIANCE WITH THE MINIMUM 10 TIMES THE |
| SUCTION PIPE DIAMETER. |
| |
| |
| 5) THE FIFTH SHEET IN THE HYDRAULIC INFOMATION TABLE |
| AND THE HYDRAULIC CALCULATION PACKAGE INDICATES AN |
| ACTUAL AREA OF 4866.67FT2. THE AREA HIGHLIGHTED DOES |
| NOT MATCH THAT TOTAL. |
| |
| PLEASE PROVIDE JUSTIFICATION OR CLEARLY INDICATE |
| CORRECTION ON REVISION SHEET. |
| |
| ADDITIONALLY, IF JUSTIFIED, PLEASE PROVIDE A REVIEW FOR |
| THE CHANGEAND APPROVAL BY THE ENGINEER OF RECORD AS |
| THIS WOULD EXCEED PREVIOUSLY SUBMITTED DOCUMENTATION'S. |
| |
| |
| 6) THERE IS NO "VALUE" INDICATED ON THE PERMIT |
| SUBMITTAL. |
| |
| PLEASE PROVIDE AN ACCURATE "VALUE" OR A COPY OF THE |
| CONTRACT AMOUNT. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |