2016-09-02 15:42:37 | PROVISOS: |
| |
| #1 POINT OF SERVICE SHALL BE AT THE PROPERTY LINE. 8" |
| DCDA MUST BE LOCATED JUST INSIDE OF YOUR PROPERTY. |
| CONTACT UTILITY CUSTOMER SERVICE SHOULD YOU NEED FIELD |
| COORDINATION AS TO THE LOCATION PLACEMENT OF THE |
| DEVICE. (561) 822-2040. |
| HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI |
| CATIONS/B ACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL. |
| |
| #2 SPECIFICATIONS FOR 8" DCDA TO BE USED AT THE POINT |
| OF SERVICE. BACKFLOW MUST ALSO BE USC APPROVED AND LEAD |
| FREE TYPE. |
| (THE CITY OF WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL HAS BEEN REVISED, MAKING KNOWN THAT "ALL |
| BACKFLOW DEVICES MUST BE LEAD FREE." |
| FOR MORE INFORMATION REFER TO THE LINK BELOW: HTTP://WP |
| B.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICATIONS/B |
| ACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL) |
| |
| #3 PROVIDE SPECIFICATION SHEET FOR FIRE HYDRANT, MODEL, |
| (MUST MEET CITY OF WPB STANDARD) SEE CITY'S APPROVED |
| MATERIAL LIST AT THIS LINK: |
| HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS |
| /FORMS,-PERMITS-APPLICATIONS |
| |