Date |
Text |
2016-09-07 11:56:09 | BUILDING PLAN REVIEW |
| NORTON MUSEUM |
| W. P. B. PERMIT: 16080215 FOUNDATION & STRUCTURAL |
| PERMIT |
| W. P. B. PERMIT: 16050912 BUILDING PERMIT |
| ADD: 1451 S. OLIVE AVE. |
| CONT: GILBANE |
| TEL: 561-236-7052 |
| E-MAIL: [email protected] MICHAEL IZZO |
| E-MAIL: [email protected] MICHAEL J BEAUMIER |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: TUES-WED. SEPT. 6-7TH / 2016 |
| ACTION: DENIED |
| |
| 1) PLEASE PROVIDE A ARCHITECTURAL SHEET OR LIFE SAFETY |
| SHEET THAT PROVIDES THE CODE ANALYSIS OF THE BUILDING. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.3.5. MINIMUM PLAN REVIEW CRITERIA |
| 107.3.5.1. COMMERCIAL BUILDINGS |
| 107.3.5.1.1. BUILDING |
| OCCUPANCY TYPES AND SQUARE FOOTAGE OF BUILDING PER |
| FLOOR. |
| TYPE OF CONSTRUCTION |
| AREA INCREASES TAKEN FOR FRONTAGE AND FIRE SPRINKLERS |
| FIRE RESISTANCE RATING OF STRUCTURAL MEMBERS |
| LIFE SAFETY FLOOR PLAN / OCCUPANT LOADS |
| |
| 2) PLEASE PROVIDE AN UPDATED INDEX OF THE STRUCTURAL |
| PAGES NOT FOUND ON THE ORIGINAL BUILDING PERMIT |
| (16050912). 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 3) PLEASE BE AWARE THIS SCOPE OF WORK REQUIRES A |
| THRESHOLD INSPECTOR, SEE F.S. THRESHOLD BUILDING FL S. |
| S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING |
| WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, |
| OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| 500 PERSONS. |
| |
| 3A)SEMI-COMPLIED. THE WRITTEN INSPECTION PLAN IS |
| WRITTEN BY THE ENGINEER OF RECORD. THE SUBMITTED PLAN |
| DID NOT HAVE A DIGITAL SIGNATURE. THIS DOCUMENT IS ALSO |
| MULTIPLE PAGES AND WOULD NEED TO IDENTIFY HOW MANY |
| PAGES ARE WITHIN THE DOCUMENT. |
| 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE |
| COVERED UNDER THE COVER SHEET OR INDEX SHEET. . |
| |
| 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| REPORTS OR OTHER DOCUMENTS. |
| 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| 3B) COMPLIED. THRESHOLD INSPECTOR FORMS: WPB AMENDMENT |
| 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| |
| 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 3D) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| DOCUMENTS BY THE CONTRACTOR. |
| |
| 3D) COMPLIED. FOR THE SPECIAL INSPECTOR PROVIDED A |
| RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. |
| |
| 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| |
| 3F) NOTICE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| IN BLACK & WHITE.. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| CONCERNING SPECIAL INSPECTORS. |
| |
| 3G)NOTICE: PLEASE CALL THE CITY OF WEST PALM BEACHS |
| AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700) |
| FOR ALL BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| |
| 3H) NOTICE. 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| PENETRATIONS, FOR WALLS AND CEILINGS. |
| |
| 4) SHEET 0277_S003 HEADING FOUNDATIONS INDICATES THERE |
| WAS A GEOTECHNICAL REPORT COMPLETED BY ARDAMAN |
| 12/16/2014. THE SUBMITTED REPORT DOES NOT HAVE AN |
| ELECTRONIC SIGNATURE AND SEAL. NOTE WHEN SUBMITTED |
| ELECTRONICALLY THE SOILS ENGINEER WILL NEED TO SUBMIT |
| UNDER AN ELECTRONIC SEAL PER 61G15-23.005 PROCEDURES |
| FOR SIGNING AND SEALING ELECTRONICALLY TRANSMITTED |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| (ELECTRONIC SEALS). |
| OTHERWISE ONE PAPER ORIGINAL SIGNED AND SEALED DOCUMENT |
| WILL BE RETAINED AND SCANNED INTO THE SYSTEM. |
| |
| 5A) COMMENT # 17 FROM THE ORIGINAL BUILDING PERMIT |
| (16050912) DEALT WITH WIND PRESSURES FOR THE BUILDING. |
| THE RESPONSE INDICATES THERE WERE SITE SPECIFIC WIND |
| TUNNEL TEST THAT WERE COMPLETED. THE WIND TUNNEL TEST |
| IS AN EXCEPTION TO SECTION 1609.1.1 WHEN THE TEST WAS |
| IN ACCORDANCE WITH CHAPTER 31 OF ASCE 7. THIS REVIEW NO |
| SUCH DOCUMENTS WERE SUBMITTED ELECTRONICALLY (SHEET |
| 0284_S010 WIND STUDY REPORT FROM WIND DESK-TOP STUDY |
| REPORT FROM EWDI 12/17/2015). A SIGNED AND SEALED PAPER |
| ORIGINAL CAN BE SUBMITTED ON THE NEXT REVIEW. THE CITY |
| WILL THEN SCAN IN THE DOCUMENT FOR RECORD RETENTION. |
| |
| 5B) COMMENT # 17 FROM THE ORIGINAL BUILDING PERMIT |
| (16050912) DEALT WITH WIND PRESSURES FOR THE BUILDING. |
| THE RESPONSE INDICATES THERE WERE SITE SPECIFIC WIND |
| TUNNEL TEST THAT WERE COMPLETED. SHEETS S008, S009,& |
| S010 ALL PROVIDE THE POSITIVE AND NEGATIVE PRESSURES |
| FOR ALL OPENINGS BUT THE PRESSURES CA NOT BE VALIDATED |
| SINCE THE WIND STUDY REPORT FROM WIND DESK-TOP STUDY |
| REPORT FROM EWDI 12/17/2015 HAS NOT BEEN SUBMITTED FOR |
| REVIEW. 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE WIND |
| TUNNEL TEST IS AN EXCEPTION TO SECTION 1609.1.1 WHEN |
| THE TEST WAS IN ACCORDANCE WITH CHAPTER 31 OF ASCE 7. |
| |
| 5C) UNDER THE STRUCTURE ONLY PERMIT THE PRESSURES ARE |
| GIVEN FOR THE EXTERIOR OPENINGS BUR THERE ARE NEITHER |
| SIZES WIDTH AND HEIGHT OF THE WINDOWS, DOORS, ROOF |
| OPENINGS FOR MECHANICAL EQUIPMENT NOR SKYLIGHTS |
| OPENINGS IN THE ROOF. HEADER AND SILL HEIGHTS FOR |
| WINDOWS AND DOORS ARE ALSO AN UNKNOWN? |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| BUILDINGS. |
| 107.3.5.1.1 COMMERCIAL BUILDING |
| BUILDING ENVELOPE |
| WALL SYSTEMS |
| |
| 5D) THE STRUCTURE AND FOUNDATION ONLY PERMIT DOES NOT |
| INDICATE IF THE CONTRACTOR IS ALSO INCLUDING THE |
| EXTERIOR COMPONENTS AND CLADDING TO BE ABLE TO SEAL OUT |
| WIND AND RAIN SINCE THE PRESSURES ARE PROVIDED FOR THE |
| WINDOWS AND DOORS? ARE EXTERIOR BLOCK WALLS AND COLUMNS |
| AND BEAMS TO BE INCLUDED? |
| |
| 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS/ MULLIONS. |
| |
| (B) WINDOWS/ MULLIONS FOR ALL PRODUCTS WITH GLAZING, |
| PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. |
| |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| |
| (D) ROOFING PRODUCTS AND ASSEMBLIES. FOR ALL ROOFING |
| PRODUCTS PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND |
| THEIR ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW |
| THE PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING |
| IS ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES |
| SHALL BE INCREASED FOR BOTH INSULATION & THE BASE SHEET |
| AS CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION |
| STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. |
| |
| (F) SKYLIGHTS |
| |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 5E) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| 5F) FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, |
| DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS |
| 1013.6 MECHANICAL EQUIPMENT. |
| GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, |
| FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT |
| REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A |
| SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL |
| EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END |
| OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT. |
| |
| 6) THE SOILS REPORT BY ARDAMAN & ASSOCIATES ON PAGE 3OF |
| 19 RECOMMENDS THE USE OF 18 INCH DIAMETER AUGER CAST |
| PILE ATTACHED TO GRADE BEAMS IN THE NORTHWEST CORNER OF |
| THE BUILDING. SHEET 285_A120.7 IS THE NORTHWEST CORNER |
| OF THE BUILDING THE FOUNDATION PLANS. IT APPEARS THE |
| RECOMMENDATION OF THE SOILS ENGINEER WAS NOT TAKEN |
| SINCE THE PLANS DO NOT SHOW AUGER-CAST PILE AND GRADE |
| BEAMS. FOR THE LOADS TO BE SUPPORTED BY THE SPREAD |
| FOUNDATIONS THE SOILS REPORT WILL NEED AN ADDENDUM |
| PROVIDING WHAT THE MINIMUM SAFE BEARING VALUE WILL BE |
| FOR THE SOIL PER SQUARE FOOT AND THE MINIMUM WIDTHS FOR |
| THE VARIOUS FOUNDATIONS FOR THE GRAVITY LOADS TO BE |
| RESISTED. FBC-B 1803.5.2 QUESTIONABLE SOILS. |
| |
| 7) THE SHEET 0285_S120.7 SHOWS A ELEVATION CHANGE IN |
| THE FINISH FLOOR LEVELS BUT THE PLANS DO NOT PROVIDE AT |
| WHAT ELEVATION EACH FLOOR LEVEL WILL BE. 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 8) SHEET 0285_S120.7 DETAIL # 20 INDICATES THE EXISTING |
| WALL AND FOUNDATION ARE GOING TO REQUIRE UNDER PINNING |
| BUT THE PLANS DO NOT INDICATE HOW THE UNDER PINNING IS |
| TO OCCUR. THE SECOND ISSUE IS THE DETAIL AS SHOWN DOES |
| NOT HAVE THE MATERIALS USED FOR UNDER PINNING CENTERED |
| ON THE FOUNDATION THAT WILL CREATE A ECCENTRIC LOADING |
| ? HOW WILL THE SOILS ON THE BACKSIDE OF THE |
| UNDERPINNING BE STABILIZED TO NOT ALLOW CAVE INS DURING |
| THE UNDERPINNING PROCESS? THE SOILS REPORT SECTION |
| 5.3.3 REFERS TO VARIOUS PROCESSES THAT COULD BE USED IN |
| THIS TYPE SITUATION. FBC-B 3307.1 PROTECTION REQUIRED. |
| |
| 9) SHEET 0285_S120.7 DETAIL #17 SHOWS A DETAIL OF THE |
| DROPPED FLOOR SECTION BUT THE DETAIL DOES NOT INDICATE |
| THE STAIRS AND TIERED SEATING. 107.2.1.3. ADDITIONAL |
| INFORMATION REQUIRED. |
| |
| 10) SHEETS 0295_S124.7 THRU 0298_S125.8 EACH OF THE |
| SHEETS INDICATE THEY ARE TO 1/8 INCH EQUALS A FOOT BUT |
| THERE IS NO SCALE OR MEASUREMENTS ON THESE SHEETS TO BE |
| ABLE TO SEE WHAT THE CENTER TO CENTER SPACING OF THE |
| FRAMING MEMBERS ARE? THE SPACING OF THE FRAMING MEMBERS |
| FOUND ON SHEET 0295_S124.7 BETWEEN GRID LINES 1.1 & 1.2 |
| AND BETWEEN 2 & 3 IS QUITE A BIT LARGER THAN FOUND ON |
| THE OTHER FRAMING SHEETS. DEPENDING ON THE TYPE OF ROOF |
| DECK AND ROOFING MATERIAL SELECTED THE SPAN LIMITATION |
| MAY BE MAXED OUT IN THE ROOFING DECK AS WELL AS THE |
| ROOFING PRODUCT APPROVAL THAT NORMALLY COMES IN AT A |
| LATER DATE. 107. 2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |