Plan Review Notes
Plan Review Notes For Permit 16080215
Permit Number 16080215
Review Stop B
Sequence Number 1
Notes
Date Text
2016-09-07 11:56:09BUILDING PLAN REVIEW
 NORTON MUSEUM
 W. P. B. PERMIT: 16080215 FOUNDATION & STRUCTURAL
 PERMIT
 W. P. B. PERMIT: 16050912 BUILDING PERMIT
 ADD: 1451 S. OLIVE AVE.
 CONT: GILBANE
 TEL: 561-236-7052
 E-MAIL: [email protected] MICHAEL IZZO
 E-MAIL: [email protected] MICHAEL J BEAUMIER
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES-WED. SEPT. 6-7TH / 2016
 ACTION: DENIED
  
 1) PLEASE PROVIDE A ARCHITECTURAL SHEET OR LIFE SAFETY
 SHEET THAT PROVIDES THE CODE ANALYSIS OF THE BUILDING.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5. MINIMUM PLAN REVIEW CRITERIA
 107.3.5.1. COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 OCCUPANCY TYPES AND SQUARE FOOTAGE OF BUILDING PER
 FLOOR.
 TYPE OF CONSTRUCTION
 AREA INCREASES TAKEN FOR FRONTAGE AND FIRE SPRINKLERS
 FIRE RESISTANCE RATING OF STRUCTURAL MEMBERS
 LIFE SAFETY FLOOR PLAN / OCCUPANT LOADS
  
 2) PLEASE PROVIDE AN UPDATED INDEX OF THE STRUCTURAL
 PAGES NOT FOUND ON THE ORIGINAL BUILDING PERMIT
 (16050912). 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3) PLEASE BE AWARE THIS SCOPE OF WORK REQUIRES A
 THRESHOLD INSPECTOR, SEE F.S. THRESHOLD BUILDING FL S.
 S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 3A)SEMI-COMPLIED. THE WRITTEN INSPECTION PLAN IS
 WRITTEN BY THE ENGINEER OF RECORD. THE SUBMITTED PLAN
 DID NOT HAVE A DIGITAL SIGNATURE. THIS DOCUMENT IS ALSO
 MULTIPLE PAGES AND WOULD NEED TO IDENTIFY HOW MANY
 PAGES ARE WITHIN THE DOCUMENT.
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET. .
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) COMPLIED. THRESHOLD INSPECTOR FORMS: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
  
 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 3D) COMPLIED. FOR THE SPECIAL INSPECTOR PROVIDED A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
  
 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 3F) NOTICE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 3G)NOTICE: PLEASE CALL THE CITY OF WEST PALM BEACHS
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR ALL BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3H) NOTICE. 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 4) SHEET 0277_S003 HEADING FOUNDATIONS INDICATES THERE
 WAS A GEOTECHNICAL REPORT COMPLETED BY ARDAMAN
 12/16/2014. THE SUBMITTED REPORT DOES NOT HAVE AN
 ELECTRONIC SIGNATURE AND SEAL. NOTE WHEN SUBMITTED
 ELECTRONICALLY THE SOILS ENGINEER WILL NEED TO SUBMIT
 UNDER AN ELECTRONIC SEAL PER 61G15-23.005 PROCEDURES
 FOR SIGNING AND SEALING ELECTRONICALLY TRANSMITTED
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 (ELECTRONIC SEALS).
 OTHERWISE ONE PAPER ORIGINAL SIGNED AND SEALED DOCUMENT
 WILL BE RETAINED AND SCANNED INTO THE SYSTEM.
  
 5A) COMMENT # 17 FROM THE ORIGINAL BUILDING PERMIT
 (16050912) DEALT WITH WIND PRESSURES FOR THE BUILDING.
 THE RESPONSE INDICATES THERE WERE SITE SPECIFIC WIND
 TUNNEL TEST THAT WERE COMPLETED. THE WIND TUNNEL TEST
 IS AN EXCEPTION TO SECTION 1609.1.1 WHEN THE TEST WAS
 IN ACCORDANCE WITH CHAPTER 31 OF ASCE 7. THIS REVIEW NO
 SUCH DOCUMENTS WERE SUBMITTED ELECTRONICALLY (SHEET
 0284_S010 WIND STUDY REPORT FROM WIND DESK-TOP STUDY
 REPORT FROM EWDI 12/17/2015). A SIGNED AND SEALED PAPER
 ORIGINAL CAN BE SUBMITTED ON THE NEXT REVIEW. THE CITY
 WILL THEN SCAN IN THE DOCUMENT FOR RECORD RETENTION.
  
 5B) COMMENT # 17 FROM THE ORIGINAL BUILDING PERMIT
 (16050912) DEALT WITH WIND PRESSURES FOR THE BUILDING.
 THE RESPONSE INDICATES THERE WERE SITE SPECIFIC WIND
 TUNNEL TEST THAT WERE COMPLETED. SHEETS S008, S009,&
 S010 ALL PROVIDE THE POSITIVE AND NEGATIVE PRESSURES
 FOR ALL OPENINGS BUT THE PRESSURES CA NOT BE VALIDATED
 SINCE THE WIND STUDY REPORT FROM WIND DESK-TOP STUDY
 REPORT FROM EWDI 12/17/2015 HAS NOT BEEN SUBMITTED FOR
 REVIEW. 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE WIND
 TUNNEL TEST IS AN EXCEPTION TO SECTION 1609.1.1 WHEN
 THE TEST WAS IN ACCORDANCE WITH CHAPTER 31 OF ASCE 7.
  
 5C) UNDER THE STRUCTURE ONLY PERMIT THE PRESSURES ARE
 GIVEN FOR THE EXTERIOR OPENINGS BUR THERE ARE NEITHER
 SIZES WIDTH AND HEIGHT OF THE WINDOWS, DOORS, ROOF
 OPENINGS FOR MECHANICAL EQUIPMENT NOR SKYLIGHTS
 OPENINGS IN THE ROOF. HEADER AND SILL HEIGHTS FOR
 WINDOWS AND DOORS ARE ALSO AN UNKNOWN?
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDING
 BUILDING ENVELOPE
 WALL SYSTEMS
  
 5D) THE STRUCTURE AND FOUNDATION ONLY PERMIT DOES NOT
 INDICATE IF THE CONTRACTOR IS ALSO INCLUDING THE
 EXTERIOR COMPONENTS AND CLADDING TO BE ABLE TO SEAL OUT
 WIND AND RAIN SINCE THE PRESSURES ARE PROVIDED FOR THE
 WINDOWS AND DOORS? ARE EXTERIOR BLOCK WALLS AND COLUMNS
 AND BEAMS TO BE INCLUDED?
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS/ MULLIONS.
  
 (B) WINDOWS/ MULLIONS FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS
 AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE.
  
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
  
 (D) ROOFING PRODUCTS AND ASSEMBLIES. FOR ALL ROOFING
 PRODUCTS PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND
 THEIR ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW
 THE PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING
 IS ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES
 SHALL BE INCREASED FOR BOTH INSULATION & THE BASE SHEET
 AS CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT.
  
 (F) SKYLIGHTS
  
 (G) PRE-ENGINEERED A/C STANDS
  
 5E) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 5F) FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS
 1013.6 MECHANICAL EQUIPMENT.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A
 SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END
 OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
  
 6) THE SOILS REPORT BY ARDAMAN & ASSOCIATES ON PAGE 3OF
 19 RECOMMENDS THE USE OF 18 INCH DIAMETER AUGER CAST
 PILE ATTACHED TO GRADE BEAMS IN THE NORTHWEST CORNER OF
 THE BUILDING. SHEET 285_A120.7 IS THE NORTHWEST CORNER
 OF THE BUILDING THE FOUNDATION PLANS. IT APPEARS THE
 RECOMMENDATION OF THE SOILS ENGINEER WAS NOT TAKEN
 SINCE THE PLANS DO NOT SHOW AUGER-CAST PILE AND GRADE
 BEAMS. FOR THE LOADS TO BE SUPPORTED BY THE SPREAD
 FOUNDATIONS THE SOILS REPORT WILL NEED AN ADDENDUM
 PROVIDING WHAT THE MINIMUM SAFE BEARING VALUE WILL BE
 FOR THE SOIL PER SQUARE FOOT AND THE MINIMUM WIDTHS FOR
 THE VARIOUS FOUNDATIONS FOR THE GRAVITY LOADS TO BE
 RESISTED. FBC-B 1803.5.2 QUESTIONABLE SOILS.
  
 7) THE SHEET 0285_S120.7 SHOWS A ELEVATION CHANGE IN
 THE FINISH FLOOR LEVELS BUT THE PLANS DO NOT PROVIDE AT
 WHAT ELEVATION EACH FLOOR LEVEL WILL BE. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 8) SHEET 0285_S120.7 DETAIL # 20 INDICATES THE EXISTING
 WALL AND FOUNDATION ARE GOING TO REQUIRE UNDER PINNING
 BUT THE PLANS DO NOT INDICATE HOW THE UNDER PINNING IS
 TO OCCUR. THE SECOND ISSUE IS THE DETAIL AS SHOWN DOES
 NOT HAVE THE MATERIALS USED FOR UNDER PINNING CENTERED
 ON THE FOUNDATION THAT WILL CREATE A ECCENTRIC LOADING
 ? HOW WILL THE SOILS ON THE BACKSIDE OF THE
 UNDERPINNING BE STABILIZED TO NOT ALLOW CAVE INS DURING
 THE UNDERPINNING PROCESS? THE SOILS REPORT SECTION
 5.3.3 REFERS TO VARIOUS PROCESSES THAT COULD BE USED IN
 THIS TYPE SITUATION. FBC-B 3307.1 PROTECTION REQUIRED.
  
 9) SHEET 0285_S120.7 DETAIL #17 SHOWS A DETAIL OF THE
 DROPPED FLOOR SECTION BUT THE DETAIL DOES NOT INDICATE
 THE STAIRS AND TIERED SEATING. 107.2.1.3. ADDITIONAL
 INFORMATION REQUIRED.
  
 10) SHEETS 0295_S124.7 THRU 0298_S125.8 EACH OF THE
 SHEETS INDICATE THEY ARE TO 1/8 INCH EQUALS A FOOT BUT
 THERE IS NO SCALE OR MEASUREMENTS ON THESE SHEETS TO BE
 ABLE TO SEE WHAT THE CENTER TO CENTER SPACING OF THE
 FRAMING MEMBERS ARE? THE SPACING OF THE FRAMING MEMBERS
 FOUND ON SHEET 0295_S124.7 BETWEEN GRID LINES 1.1 & 1.2
 AND BETWEEN 2 & 3 IS QUITE A BIT LARGER THAN FOUND ON
 THE OTHER FRAMING SHEETS. DEPENDING ON THE TYPE OF ROOF
 DECK AND ROOFING MATERIAL SELECTED THE SPAN LIMITATION
 MAY BE MAXED OUT IN THE ROOFING DECK AS WELL AS THE
 ROOFING PRODUCT APPROVAL THAT NORMALLY COMES IN AT A
 LATER DATE. 107. 2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  