2016-08-12 07:44:18 | |
| BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16080184 |
| ADD: 3700 S. DIXIE HWY. SUITES 5-6 |
| CONT: ANDERSON CONSTRUCTION |
| TEL: 5561-255-5464 |
| E-MAIL: INFO@ADERSON CONSTRUCTIONFL.COM |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. AUGUST 12/ 2016 |
| ACTION: DENIED |
| |
| 1) PLEASE NOTE THERE IS NO HEADERSTRIP ON THE PLANS |
| PROVIDING AN ADDRESS WHERE THE WORK IS GOING TO OCCURR. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE |
| PROPOSED PROJECT. |
| |
| 2) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.3.5. MINIMUM PLAN REVIEW CRITERIA |
| FOR COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| OCCUPANCY TYPE: |
| MINIMUM BUILDING TYPE |
| FIRE SPRINKLERED OR NOT |
| SQ. FT. OF BUILDING. |
| SQ. FT. OF TENANT SPACE |
| OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| EXIT ACCESS |
| EXIT |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| |
| 3)THE CONTRACTOR OF RECORD (QAULIFIER) THAT CREATE THE |
| PLAN FOR THE PROPOSED WORK WILL NEED TO PRINT THEIR |
| NAME, SIGN THEIR NAME & PRINT THEIR LICENSE NUMBER ON |
| THE PLANS THEY HAVE CREATED. 2014 FLORIDA BUILDING CODE |
| W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.1. |
| 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED |
| UNDER THE PROVISIONS OF SECTION 489.115 FLORIDA |
| STATUTES, SHALL BE CONSIDERED EQUIVALENT TO SEALED |
| PLANS AND SPECIFICATIONS BY A PERSON LICENSED UNDER |
| CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 FLORIDA |
| STATUTES. |
| |
| 4) PLANS NEED TO BE BOUND TOGETHER INTO ONE SET OF |
| DOCUMENTS BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. THE |
| BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, |
| IN |
| ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| PROGRAM. |
| |
| 5) PLEASE INDICATE WHICH WAY THE CEILING/ RAFTER/ OR |
| ROOF JOIST ARE POSITIONED. THE TENANT SEPARATION WALL |
| MAY ALSO BE A BEARING WALL, REQUIRING A PROPERLY SIZED |
| HEADER, JACK STUDS AND FULL LENGTH BEARING STUDS. THIS |
| SAME WALL IF IT IS A BEARING WALL WOULD ALSO BE |
| CONSIDERED PART OF THE MWFRS (MAIN WIND FORCE RESISTING |
| SYSTEM) IN THAT CASE THE CONTRACTOR CAN NOT DESIGN |
| LOADS TO RESIST WIND LOADS UNLESS CERTIFIED THEOUGH A |
| STATE APPROVED COURSE, THIS COURSE AND CERTIFICATE WAS |
| FOR |
| WIND LOADS ON ONE & TWO FAMILY RESIDENCE. |
| |
| 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED |
| UNDER THE PROVISIONS OF SECTION489.115 FLORIDA |
| STATUTES, SHALL BE CONSIDERED EQUIVALENT TO SEALED |
| PLANS AND SPECIFICATIONS BY A PERSON LICENSED UNDER |
| CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 FLORIDA |
| STATUTES, BY LOCAL ENFORCEMENT AGENCIES FOR PLANS |
| REVIEW FOR PERMITTING PURPOSES RELATING TO COMPLIANCE |
| WITH THE WIND-RESISTANCE PROVISIONS OF THE CODE OR |
| ALTERNATE METHODOLOGIES ENFORCEMENT AGENCIES MAY RELY |
| UPON SUCH CERTIFICATION BY CONTRACTORS THAT THE PLANS |
| AND SPECIFICATIONS SUBMITTED CONFORM TO THE |
| REQUIREMENTS OF THE CODE FOR WIND RESISTANCE. UPON GOOD |
| CAUSE SHOWN, LOCAL GOVERNMENT CODE ENFORCEMENT AGENCIES |
| MAY ACCEPT OR REJECT PLANS SEALED BY PERSONS LICENSED |
| UNDER CHAPTERS 471,481 OR 489, FLORIDA STATUTES. |
| |
| 6) THE PLANS INDICATE THE CONTRACT VALUE OF THE PROJECT |
| IS $ 4,200.00 DOLLARS. 20% OF THE CONTRACT VALUE OR |
| $840.00 DOLLARS IS TO BE SPENT ON ACCESSIBLE UPGRADES. |
| PLEASE SEE THE ORDER THE FUNDS ARE TO BE SPENT. THE |
| CONTRACTOR IS TO PROVIDE AN ITEMIZED LIST INTHE ORDER |
| LISTED BELOW OF WHAT ACCESSIBLE ELEMENTS ARE GOING TO |
| BE UPGRADED TO CODE COMPLIANCE. |
| 2014 FBC-ACCESSIBILITY CODE. 202.4.1 DISPROPORTIONATE |
| COST. ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| AN INACCESSIBLE DRINKING FOUNTAIN. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |