2016-08-05 16:50:401ST REVIEW FBC-2014 MECHANICAL
 PERMIT 16080172
 8/5/16
  
 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL ON THE PLAN.
 A NEW HEAT PUMP IS SHOWN ON THE PLAN- CLARIFY IF THIS
 IS AN EXACT SIZE CHANGOUT AND SUBMIT AN AC CHANGEOUT
 FORM IF APPLICABLE. . OTHERWISE PROVIDE COOLING AND
 HEATING CALCULATIONS AS REQUIRED BY SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
  
 2) SHOW LOCATIONS OF AC DUCT, DIFFUSER, OR RETURN GRILL
 ALTERATIONS AND PROVIDE DETAILS IF APPLICABLE.
  