2016-08-11 14:44:52ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: TOUB RESIDENCE/REMODEL
 JOB ADDRESS: 221 POTTER ROAD
 DESCRIPTION: REMOVE EXISTING GENERATOR & RELOCATE W/NEW
 GENERATOR PER PLANS
 MASTER PERMIT: 16080116
 REVISION:
  
 BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL
 REVIEW:
  
 1. NEC 702.4(B): PROVIDE LOAD CALCS IN ACCORDANCE W/NEC
 220.
 2. NEC 702.4(B)(2): STANDBY GENERATOR SHALL BE CAPABLE
 OF SUPPLYING THE FULL LOAD APPLIED, OR ATS NOT
 PERMITTED W/O ACCEPTABLE LOAD SHED PROVISIONS.
 3. ON THE FLOOR PLAN NOTE THE LOCATION OF ALL SERVICE
 EQUIPMENT AS WELL AS ALL ELECTRICAL PANELS.
 4. NEC 215.5: PROVIDE A SITE SPECIFIC RISER DIAGRAM
 SHOWING THE LOCATION AND POSITION IN THE SERVICE OF THE
 TRANSFER SWITCH WITH RELATION TO ALL OTHER PANELS.
 INCLUDE ON THE RISER DIAGRAM CONDUCTOR SIZING.
 5. NEC 250.104(B): SHOW ON PLANS WHERE THE GAS LINE IS
 BONDED. EQUIPMENT BONDING CONDUCTOR PER NEC 250.122.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER