Plan Review Notes For Permit 16080089 |
Permit Number |
16080089 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-08-15 17:41:15 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | - PASSED WITH THE FOLLOWING PROVISO. [ RED LINED ON | | PLANS ] | | | | - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT, | | SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET | | SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE | | SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE | | LOCATED WITHIN 25 FT. OF THE EQUIPMENT. |
|