2016-08-15 17:41:15REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - PASSED WITH THE FOLLOWING PROVISO. [ RED LINED ON
 PLANS ]
  
 - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT,
 SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
 SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED WITHIN 25 FT. OF THE EQUIPMENT.