Plan Review Notes
Plan Review Notes For Permit 16080089
Permit Number 16080089
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-04 10:41:00REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - PROVIDE A SITE SPECIFIC PLAN SHOWING A/C DISCONNECT
 WITHIN SIGHT FOR BOTH INDOOR AND OUTDOOR UNITS PER NEC
 440
  
 - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT,
 SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
 SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED WITHIN 25 FT. OF THE EQUIPMENT.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved