Plan Review Notes For Permit 16080071 |
Permit Number |
16080071 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-03 13:28:48 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | PASSED WITH THE FOLLOWING PROVISO'S | | | | 1) SITE THE CURRENT APPLICABLE CODES FBC-2014 5TH | | EDITION AND NEC 2011 | | | | 2) IN ADDITION TO THE OUTDOOR OUTLET ENCLOSURE BEING | | "WP" THE GFCI RECEPTACLE ITSELF SHALL BE "WR" PER NEC | | 406.9(B) | | | | 3) FINAL AS BUILTS PLANS SHALL REFLECT THESE RED LINED | | CHANGES ! |
|