Plan Review Notes For Permit 16080066 |
Permit Number |
16080066 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-09-21 11:50:22 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #16080066 | | 9/21/16 | | | | 1) SUPPLY DUCT AND CHILLED WATER PIPE SIZES NOT SHOWN. | | SHOW THE POINT OF CONNECTIONFOR THE CHILLED WATER | | PIPING. | | | | 2) THE PLAN DOES NOT CLEARLY INDICATE HOW O/A IS BEING | | PROVIDED. DOES THE NEW 6" DUCT CONNECT TO AN EXISTING | | O/A DUCT- PLEASE CLARIFY. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|