2016-09-21 11:50:223RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16080066
 9/21/16
  
 1) SUPPLY DUCT AND CHILLED WATER PIPE SIZES NOT SHOWN.
 SHOW THE POINT OF CONNECTIONFOR THE CHILLED WATER
 PIPING.
  
 2) THE PLAN DOES NOT CLEARLY INDICATE HOW O/A IS BEING
 PROVIDED. DOES THE NEW 6" DUCT CONNECT TO AN EXISTING
 O/A DUCT- PLEASE CLARIFY.
  