2016-08-31 11:31:25 | 2ND REVIEW FBC-2014 MECHANICAL |
| PERMIT #16080066 |
| 8/31/16 |
| |
| PLEASE REVIEW THE 1ST REVIEW COMMENTS PRINTED BELOW |
| REGARDING THE AC PLAN. THE COMMENTS REMAIN APPLICABLE |
| TO THE RESUBMITTED PLANS. IN ADDITION PLEASE NOTE THE |
| FOLLOWING: THE INSTALLING AC CONTRACTOR MAY DRAW, SIGN, |
| AND SUBMIT AC PLANS, BUT MUST ALSO SUBMIT A SUB-PERMIT |
| APPLICATION. THE INSTALL AC CONTRACTOR'S PLANS MUST |
| SHOW ONLY DETAILS FOR THE AC SYSTEM, AND NOT CONTAIN |
| |
| ANY ARCHITECTURAL DETAILS AND SCHEDULES PREPARED BY THE |
| ARCHITECT OF RECORD. THE WPB BUILDING DEPT. IS |
| REQUIRING A SIGNED AND SEALED LETTER FROM THE ARCHITECT |
| OF RECORD HARVARD JOLLY STATING THAT THEY ARE NOT |
| PROVIDING THE DESIGN OF THE MEP SYSTEMS, HOWEVER THEY |
| MAY ALLOW THE CONTRACTOR TO USE THEIR FLOOR PLAN OR |
| REFLECTIVE CEILING DRAWING AS THE BASIS FOR THE AC |
| SYSTEM PLANS. |
| |
| 1) TWO A1.1 PLANS SHEETS HAVE BEEN SUBMITTED. ONE SHEET |
| IS SIGNED AND SEALED BY THE ARCHITECT OF RECORD- RENE |
| TERCILLA AIA. THE OTHER A1.1 PLAN SHEET IS NOT SIGNED |
| AND SEALED AND HAS A HANDWRITTEN AC PLAN AND NOTES |
| WRITTEN OVER THE CEILING DETAIL. THIS PLAN WILL NOT BE |
| REVIEWED AND MUST BE DISCARDED PER FLORIDA STATUTE |
| 481.221(2), FLORIDA ADMINISTRATIVE CODE 61G1-16.003. |
| |
| 2) REFER TO SECTION 107.1 WPB AMENDMENTS TO THE FBC AND |
| RESUBMIT MECHANICAL PLANS THAT INCLUDE: A SCOPE OF WORK |
| OUTLINE FOR THE PROJECT, AC EQUIPMENT SCHEDULE, DUCT |
| LAYOUT PLAN, AIR DISTRIBUTION AND DEVICE SCHEDULES, |
| COOLING AND HEATING CALCULATIONS, CONDENSATE DISPOSAL, |
| O/A CALCULATIONS AND CONTROLS, ENERGY COMPLIANCE, SMOKE |
| AND FIRE PROTECTION TRANSFER OPENING PROTECTIONS, |
| FIRESTOPPING DETAILS, AND DUCT HANGING AND SUPPORT |
| DETAILS. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |
| [email protected] |
| |