2016-08-08 14:09:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1. COVER SHEET - THERE IS NO INDICATION TO A REFERENCED
 FIRE CODE COMPLIANCE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
  
  
 2. SHEET A 1.1 - THERE WERE THREE (3) SHEETS INDICATED
 AS A 1.1. ONLY OFFICIAL SHEETS SHALL BE SUBMITTED.
  
 PLEASE CORRECT OR CLARIFY.
  
  
  
 3. COVER SHEET - THERE IS NO INDICATIONS OF ANY
 ENGINEERED LIFE SAFETY SYSTEM(S), I.E. FIRE SPRINKLER
 OR FIRE ALARM.
  
 THE EXTENT OF THE REMODEL OR REVISION IS UNCLEAR AND
 DOES NOT INDICATE SUFFICIENT DETAIL TO ADDRESS LIFE
 SAFETY CONCERNS OF THE PROPOSED PROJECT.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
 PLEASE PROVIDE A NOTE INDICATING ANY EXISTING SYSTEM(3)
 AND THAT ALL WORK RELATED TO THE FIRE SPRINKLER AND/OR
 FIRE ALARM SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS
 BY CERITIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 4. ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  