2016-08-08 14:09:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1. COVER SHEET - THERE IS NO INDICATION TO A REFERENCED |
| FIRE CODE COMPLIANCE. |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| APPLICABLE CODES OR STANDARDS. |
| |
| |
| |
| 2. SHEET A 1.1 - THERE WERE THREE (3) SHEETS INDICATED |
| AS A 1.1. ONLY OFFICIAL SHEETS SHALL BE SUBMITTED. |
| |
| PLEASE CORRECT OR CLARIFY. |
| |
| |
| |
| 3. COVER SHEET - THERE IS NO INDICATIONS OF ANY |
| ENGINEERED LIFE SAFETY SYSTEM(S), I.E. FIRE SPRINKLER |
| OR FIRE ALARM. |
| |
| THE EXTENT OF THE REMODEL OR REVISION IS UNCLEAR AND |
| DOES NOT INDICATE SUFFICIENT DETAIL TO ADDRESS LIFE |
| SAFETY CONCERNS OF THE PROPOSED PROJECT. |
| |
| ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR |
| CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND |
| SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY |
| CERTIFIED LIFE SAFETY CONTRACTORS. |
| THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| CONSTRUCTION PERIOD. |
| ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| AND COMPLETE PROTECTION IS RETURNED. |
| |
| |
| PLEASE PROVIDE A NOTE INDICATING ANY EXISTING SYSTEM(3) |
| AND THAT ALL WORK RELATED TO THE FIRE SPRINKLER AND/OR |
| FIRE ALARM SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS |
| BY CERITIFIED LIFE SAFETY CONTRACTORS. |
| |
| |
| |
| 4. ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |