Plan Review Notes
Plan Review Notes For Permit 16080066
Permit Number 16080066
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-04 10:16:35REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - DESIGNER OF RECORD CONFLICT PER FLORIDA STATUE 481,
 IF THE INTENT IS TO USE DRAWINGS AS A TEMPLATE PLEASE
 REMOVE ARCHITECT TILTE BLOCK. THERE COULD BE A
 COPYWRITE ISSUE PLEASE CLARIFY ?
  
 - NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL BE
 FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.
  
 - LOW VOLTAGE SHALL BE UNDER A SEPERATE PERMIT.