2016-08-12 06:15:45 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16080066 |
| ADD: 303 BANYAN BLVD. 3RD FLOOR/ NEW CONFERENCE ROOM. |
| CONT: IBIS BUILDING |
| TEL: 561-568-2570 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. AUGUST 12/ 2016 |
| ACTION: DENIED |
| |
| 1) PLEASE NOTE (3) A1.1 FLOOR PLANS WERE SUBMITTED ONLY |
| ONE WAS SIGNED AND SEALED BY THE DESIGNER OF RECORD. |
| PLEASE NOTE ON THE OTHER TWO SHEETS ONE MECHANICAL |
| SYSTEMS WAS DRAWN IN THE OTHER ELECTRICAL SYSTEMS WERE |
| DRAWN IN. IF THIS IS NOT WORK COMPLETED BY THE DESIGNER |
| OF RECORD, THE AUTHOR OF THESE SHEETS ARE VIOLATING |
| COPYRIGHT LAWS. PLEASE NOTE THERE ARE NO ELECTRICAL NOR |
| MECHANICAL CONTRACTORS SIGNED ON AS SUB-PERMITS. ONLY |
| THE QUALIFIER FOR EACH OF THOUGHS COMPANIES ELECTRICAL |
| & MECHANICAL CAN DEVELOP THEIR OWN PLAN UNDER THERE |
| LICENSE. THEY WILL NEED TO PRINT THEIR NAME SIGN THEIR |
| NAME AND PRINT THEIR LICENSE NUMBER ON THE DOCUMENT |
| THEY CREATED. THEY CAN NOT CREATE A DOCUMENT FOR |
| ANOTHER CONTRACTOR IT HAS TO BE THE PROPOSED WORK THEIR |
| COMPANY IS LICENSED FOR AND WORK THEY WILL BE |
| PREFORMING UNDER THEIR LICENSE. 2014 FLORIDA BUILDING |
| CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.1. |
| 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED |
| UNDER THE PROVISIONS OF SECTION 489.115 FLORIDA |
| STATUTES, SHALL BE CONSIDERED EQUIVALENT TO SEALED |
| PLANS AND SPECIFICATIONS BY A PERSON LICENSED UNDER |
| CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 FLORIDA |
| STATUTES. |
| |
| 2) PLANS NEED TO BE BOUND TOGETHER INTO ONE SET OF |
| DOCUMENTS BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. THE |
| BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, |
| IN |
| ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| PROGRAM. |
| |
| 3) SHEET A1.1 INDICATES 6 UL WALL PENETRATION SYSTEMS |
| BUT DOES NOT PROVIDE THE UL DOCUMENTATION FOR EACH |
| SYSTEM WHAT MAKES UP EACH SYSTEM. THE FIELD INSPECTORS |
| NEED THIS INFORMATION TO SEE WHAT COMPONENTS EACH |
| SYSTEM IS MADE FROM, AND THE LIMITATIONS ON EACH |
| SYSTEM. PROVIDE DOCUMENTATION. |
| 714.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH |
| PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN |
| ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM |
| POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) |
| OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN |
| THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL |
| PENETRATED. |
| |
| 4) WITH THIS NEW TENANT SPACE THERE WILL BE MORE LIKELY |
| A NEW FIRE SPRINKLER LAYOUT REQUIRED. PLEASE NOTE WHEN |
| LESS THAN 50 SPRINKLER HEADS ARE BEING MOVED, THE PLANS |
| CAN BE CREATED BY THE FIRE SPRINKLER CONTRACTOR. |
| 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED |
| UNDER THE PROVISIONS OF SECTION 489.115 FLORIDA |
| STATUTES, SHALL BE CONSIDERED EQUIVALENT TO SEALED |
| PLANS AND SPECIFICATIONS BY A PERSON LICENSED UNDER |
| CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 FLORIDA |
| STATUTES. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |