2016-09-27 19:36:39ELECTRICAL REVIEW APPROVED. ALL PREVIOUSLY MENTIONED
 DEFICIENCIES HAVE BEEN SATISFACTORILY ADDRESSED.
2016-09-23 10:12:313RD ELECTRICAL REVIEW:
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME: DOCK/PIER & SEAWALL
 JOB ADDRESS: 3200 WASHINGTON RD.
 DESCRIPTION: REPAIR 102 FT. OF SEAWALL; REPLACE DOCK
 W/PIER, ACCESS PIER AND PLATFORM. INSTALL A 16K & A 10K
 LB. FOUR POLE BOAT LIFT.
 MASTER PERMIT: 16080055
  
 0. NOW THAT AN ELECTRICAL SHEET HAS BEEN PROVIDED,
 BELOW ARE THE DEFICIENCIES NOTED AT THE TIME OF THE
 ELECTRICAL PLAN REVIEW.
 SECTION 107.2.1.4 OF THE WPB CITY AMENDMENTS TO THE
 FBC-B REQUIRES THAT BUILDING PLANS BE DRAWN TO A
 MINIMUM 1/8? SCALE. THE PLANS SUBMITTED ARE WAY TOO
 SMALL TO BE LEGIBLE.
 1. PROVIDE PROOF OF THE REQUIRED LONGSHORE & HARBOR
 WORKERS COMPENSATION INSURANCE.
 YOU WERE PREVIOUSLY ASKED TO PROVIDE PROOF OF LONGSHORE
 & HARBOR WORKERS COMP AS REQUIRED BY TITLE 33 CHAP 18
 OF THE DEPT. OF LABOR.
 2. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE
 THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE,
 THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND
 SIGNATURE SHALL APPEAR ON ALL DOCUMENTS).
 THE DOCUMENTS ARE NOT YET SIGNED AS REQUIRED.
 3. YOU SHALL INCLUDE ON THE SITE DRAWING THE LOCATION
 OF THE OVERCURRENT PROTECTION AND OR DISCONNECTS FOR
 THE PIER.
 THERE SHALL BE A READILY ACCESSIBLE DISCONNECT ON LAND
 TO DISCONNECT ALL POWER TO THE PIER.
 4. YOU WILL NEED TO PROVIDE A WIRING DIAGRAM AND LOAD
 CALCS FOR THE PROPOSED INSTALLATION INCLUDING THE
 INDIVIDUAL MOTOR LOADS.
 YOU MENTIONED THE CONCURRENT LOADS BETWEEN THE SHORE
 POWER AND LIFT, BUT LOAD CALCS SHALL BE PROVIDED. YOU
 MAY CONSIDER IN THE CALCS EACH LIFT AS A UNIT.
 5. IF THE POWER WILL BE PROVIDED UNDER A SEPARATE
 PERMIT, YOU NEED TO PROVIDE THAT NUMBER AND INCLUDE ON
 THE DRAWING THE AVAILABLE POWER.
 SATISFIED: POWER TO PIER PROVIDED UNDER PERMIT
 16071076.
 6. FBC?R4002.9 NEC 406.9(B) RECEPTACLES IN WET
 LOCATIONS: 15 AND 20 AMPERE, 125 AND 250 VOLT
 RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE AN
 ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE
 ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20 AMPERE,
 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL BE LISTED
 WEATHER?RESISTANT TYPE WR. THIS APPLIES TO THE OUTLETS
 IN THE PEDESTAL AS WELL.
 SATISFIED: THE OUTLETS INSTALLED ON THE PEDESTALS
 COMPLY WITH THIS REQUIREMENT, BUT YOU MAY HAVE TO
 REPLACE THE OUTLETS WITH ONES THAT ARE LISTED WEATHER
 RESISTANT AS REQUIRED BY CODE.
 7. NEC 555.19(B)(2): ALL RECEPTACLES OTHER THAN THOSE
 DESIGNATED FOR SHORE POWER SHALL BE MARKED TO INDICATE
 THAT THEY ARE NOT TO BE USED FOR SHORE POWER TO BOATS.
 THIS CAN BE ADDRESSED WITH A BLOCK NOTE TO BE VERIFIED
 IN THE FIELD.
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER