Plan Review Notes
Plan Review Notes For Permit 16080055
Permit Number 16080055
Review Stop E
Sequence Number 2
Notes
Date Text
2016-08-31 13:51:562ND ELECTRICAL REVIEW:
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME: DOCK/PIER & SEAWALL
 JOB ADDRESS: 3200 WASHINGTON RD.
 DESCRIPTION: REPAIR 102 FT. OF SEAWALL; REPLACE DOCK
 W/PIER, ACCESS PIER AND PLATFORM. INSTALL A 16K & A 10K
 LB. FOUR POLE BOAT LIFT.
 MASTER PERMIT: 16080055
  
 NOW THAT AN ELECTRICAL SHEET HAS BEEN PROVIDED, BELOW
 ARE THE DEFICIENCIES NOTED AT THE TIME OF THE
 ELECTRICAL PLAN REVIEW.
  
 1. PROVIDE PROOF OF THE REQUIRED LONGSHOREMAN?S WORKERS
 COMPENSATION INSURANCE.
 2. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE
 THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE,
 THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND
 SIGNATURE SHALL APPEAR ON ALL DOCUMENTS).
 3. YOU SHALL INCLUDE ON THE SITE DRAWING THE LOCATION
 OF THE OVERCURRENT PROTECTION AND OR DISCONNECTS FOR
 THE PIER.
 4. YOU WILL NEED TO PROVIDE A WIRING DIAGRAM AND LOAD
 CALCS FOR THE PROPOSED INSTALLATION INCLUDING THE
 INDIVIDUAL MOTOR LOADS.
 5. IF THE POWER WILL BE PROVIDED UNDER A SEPARATE
 PERMIT, YOU NEED TO PROVIDE THAT NUMBER AND INCLUDE ON
 THE DRAWING THE AVAILABLE POWER.
 6. FBC-R4002.9 NEC 406.9(B) RECEPTACLES IN WET
 LOCATIONS: 15 AND 20 AMPERE, 125 AND 250 VOLT
 RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE AN
 ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE
 ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20 AMPERE,
 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE ?WR?. THIS APPLIES TO THE
 OUTLETS IN THE PEDESTAL AS WELL.
 7. NEC 555.19(B)(2): ALL RECEPTACLES OTHER THAN THOSE
 DESIGNATED FOR SHORE POWER SHALL BE MARKED TO INDICATE
 THAT THEY ARE NOT TO BE USED FOR SHORE POWER TO BOATS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved