Plan Review Notes For Permit 16080055 |
Permit Number |
16080055 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-08 19:17:25 | ELECTRICAL REVIEW NOTES | | REVIEWED FOR COMPLIANCE WITH: | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | PROJECT NAME: DOCK/PIERS/SEAWALL | | JOB ADDRESS: 3200 WASHINGTON RD. | | DESCRIPTION: REPAIR 102? OF SEAWALL; REPLACE DOCK | | W/PIER, ACCESS PIER AND PLATFORM. INSTALL A 16K & 10K | | LB. FOUR POLE BOAT LIFT. | | MASTER PERMIT: 16080055 | | | | 1. THE SUBMITTED DRAWINGS DO NOT INCLUDE ELECTRICAL | | DATA FOR THE LIFTS. YOU SHALL PROVIDE AN ELECTRICAL | | PLAN SHOWING THE LOCATION OF THE POWER SOURCE AS WELL | | AS THE INTENDED WIRING METHOD. ALL TERMINAL CONNECTIONS | | INCLUDING THE REQUIRED DISCONNECT AND CONVENIENCE GFI | | OUTLETS. | | 2. YOU SHALL PROVIDE SITE SPECIFIC LOAD CALCS AND | | VOLTAGE DROP CALCULATIONS. | | 3. ALL WORK SHALL COMPLY WITH NEC SECTION 682 | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] |
|