Plan Review Notes
Plan Review Notes For Permit 16080044
Permit Number 16080044
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-03 14:32:13ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: INTERIOR BUILDING RENOVATIONS - COMMON
 AREAS
 JOB ADDRESS: 324 DATURA ST.
 DESCRIPTION: INTERIOR BUILDING RENOVATIONS - COMMON
 AREAS
 MASTER PERMIT:16080044
  
  
 1. THERE SEEMS TO BE A MIX UP WITH THIS SUBMITTAL. THE
 PERMIT APPLICATION DOES NOT CLEARLY IDENTIFY THE AREA
 OF WORK. THERE ARE TWO SEPARATE PLAN SETS ONE OF WHICH
 IS THE ARCHITECTURAL AND THE OTHER THE MEP AND THEY DO
 NOT MATCH. THE ELECTRICAL SET DOES NOT INDICATE THE
 AREA DRAWN WHILE THE ARCHITECTURAL SET ADDRESSES
 SEVERAL FLOORS. PLEASE PROVIDE ONE COMPLETE SET AND
 HAVE IT ALL MATCH.
 2. WITHOUT A DEFINED AREA OF WORK AND KNOWLEDGE OF WHAT
 ARE THE EXITS IT IS IMPRACTICABLE TO DETERMINE PROPER
 EXIT LIGHT PLACEMENT. CORRECT THE PLANS ACCORDINGLY.
 3. YOU SHALL INCLUDE A LIGHT DENSITY ALLOWANCE CHART AS
 INDICATED IN THE FBC-E 405.5.2
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  