2016-08-03 14:32:13 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: INTERIOR BUILDING RENOVATIONS - COMMON |
| AREAS |
| JOB ADDRESS: 324 DATURA ST. |
| DESCRIPTION: INTERIOR BUILDING RENOVATIONS - COMMON |
| AREAS |
| MASTER PERMIT:16080044 |
| |
| |
| 1. THERE SEEMS TO BE A MIX UP WITH THIS SUBMITTAL. THE |
| PERMIT APPLICATION DOES NOT CLEARLY IDENTIFY THE AREA |
| OF WORK. THERE ARE TWO SEPARATE PLAN SETS ONE OF WHICH |
| IS THE ARCHITECTURAL AND THE OTHER THE MEP AND THEY DO |
| NOT MATCH. THE ELECTRICAL SET DOES NOT INDICATE THE |
| AREA DRAWN WHILE THE ARCHITECTURAL SET ADDRESSES |
| SEVERAL FLOORS. PLEASE PROVIDE ONE COMPLETE SET AND |
| HAVE IT ALL MATCH. |
| 2. WITHOUT A DEFINED AREA OF WORK AND KNOWLEDGE OF WHAT |
| ARE THE EXITS IT IS IMPRACTICABLE TO DETERMINE PROPER |
| EXIT LIGHT PLACEMENT. CORRECT THE PLANS ACCORDINGLY. |
| 3. YOU SHALL INCLUDE A LIGHT DENSITY ALLOWANCE CHART AS |
| INDICATED IN THE FBC-E 405.5.2 |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |