Date |
Text |
2016-08-09 07:45:49 | |
| |
| BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16080044 |
| ADD: 324 DATURA ST./ LOBBY |
| CONT: GERALD CONTRACTING |
| TEL: 561-832-9785 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. TUES. AUGUST 09/2016 |
| ACTION: DENIED |
| |
| 1) PLEASE NOTE THERE IS A DISCREPANCY IN THE SCOPE OF |
| WORK BETWEEN THE PERMIT APPLICATION AND THE SCOPE OF |
| WORK THE ARCHITECT DESCRIBES ON THE COVER SHEET. THE |
| PERMIT APPLICATION UNDER THE BOX #4 FOR LOCATION OF |
| PROJECT LIST 324 DATURA ST. WRITTEN IN IS LOBBY. THE |
| ARCHITECTS SCOPE OF WORK INCLUDES RENOVATION WORK OF |
| SOME TENANT SPACES AND CONSTRUCTION OF NEW STAIRS AND |
| RAILINGS AT 2ND FLOOR/ 3RD FLOOR ATRIUM. DISCREPANCY, |
| ADDITIONAL INFORMATION IS REQUIRED. 1067.2.1.3. |
| |
| 2) THE COVER SHEET LIST THIS BUILDING TYPE AS A TYPE |
| IB- UNPROTECTED/ SPRINKLERED. PLEASE REVIEW THE 2014 |
| FBC-B TABLE 601 BUILDING TYPE IB IS PROTECTED 2 HRSFOR |
| ALL STRUCTURAL MEMBERS WITH THE EXCEPTION OF THE ROOF |
| CONSTRUCTION AND SECONDARY MEMBERS WHICH ARE TO BE 1 |
| HR. ALSO SEE FOOTNOTES B & C. |
| |
| 3) NEITHER THE COVERSHEET NOR SHEET LS-1 SHOW UNDER THE |
| EXISITNG BUILDING CODE TO WHAT METHOD OF COMPLIANCE THE |
| PLANS WERE DEVELOPED, 2014 FBC-EXISITNG BUILDING CODE |
| 301.1. |
| 301.1. THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, |
| ADDITION OR RELOCATION OF ALL EXISTING BUILDINGS SHALL |
| COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS |
| 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT. |
| APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR |
| ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A |
| SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE |
| OFFICIAL. |
| |
| 4) CLARIFICATION IS NEEDED. THE COVERSHEET INDICATES |
| UNDER SCOPE OF WORK THE CONSTRUCTION OF NEW STAIR AND |
| RAILING AT ATRIUM 2ND & 3RD FLOOR. SHEETS A-2.0 & A-3.0 |
| ONLY INDICATE PORTIONS OF RAIING ARE TO BE REPLACED. |
| THE RAILING NEEDS TO BE DEFIND TO HANDRAILS, GUARD |
| RAILS OF THE SPIRAL STAIR OR THE ATRIUM GUARDRAIL FOR |
| THE 2ND & 3RD FLOORS. SHEET A-3.0 HAS A DETAIL FOR THE |
| RAILINGS: |
| |
| 4A) THE PLANS INDICATE THE GUARDRAIL ON THE 2ND & 3RD |
| FLOOR ATRIUM ARE TO HAVE DECRATIVE INSET PANELS. THERE |
| IS NO INFORMATION ABOUT THESE PANELS, IF GLASS OR WHAT |
| MATERIALS? |
| |
| 1607.8.1 HANDRAILS AND GUARDS. HANDRAILS AND GUARDS |
| SHALL BE DESIGNED TO RESIST A LINEAR LOAD OF 50 POUNDS |
| PER LINEAR FOOT (PLF) (0.73 KN/M) IN ACCORDANCE WITH |
| SECTION 4.5.1 OF ASCE 7. GLASS HANDRAIL ASSEMBLIES AND |
| GUARDS SHALL ALSO COMPLY WITH SECTION 2407. |
| |
| 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND GUARDS |
| SHALL ALSO BE DESIGNED TO RESIST A CONCENTRATED LOAD OF |
| 200 POUNDS (0.89 KN) IN ACCORDANCE WITH SECTION 4.5.1 |
| OF ASCE 7. |
| |
| 4B) THE OTHER ISSUE IS NOTE, EXISTING 3 INCH PIPE TO |
| REMAIN TYPICAL ( CUT AND REMOVE RAILING AS NECESSARY). |
| HOW ARE THE STRUCTURAL LOADS TO BE RESTRAINED!!! |
| FBC-B 1607.8.1 & 1607.8.1.1. |
| |
| 5) THE 1ST FLOOR WHERE THERE WERE WALLS DEMOLISHED, THE |
| NEW TENANT WALLS ARE IDENTIFIED WITH A WALL TYPE 2 BUT |
| THE WALL LEGEND DOES NOT INDICATE WHICH WALLS ARE WALL |
| TYPE 1 OR 2? |
| ADDITIONAL INFORMATION IS REQUIRED. 404.6 ENCLOSURE OF |
| ATRIUMS. ATRIUM SPACES SHALL BE SEPARATED FROM ADJACENT |
| SPACES BY A 1-HOUR FIRE BARRIER CONSTRUCTED IN |
| ACCORDANCE WITH SECTION 707 OR A HORIZONTAL ASSEMBLY |
| CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH. |
| DOORS WILL ALSO NEED TO BE IDENTIFIED FOR FIRE RATINGS |
| FBC-B TABLE 716.5. |
| |
| 5) PLEASE NOTE THE CUBIC FEET OF THE ATRIUM HAS |
| INCREASED WITH THE REMOVAL OF THE WALLS ON THE 1ST |
| FLOOR. PLEASE SHOW THAT THE EXISITNG SMOKE CONTROL |
| SYSTEM WILL HANDLE THE ADDITIONAL CUBIC FEET? 2014 |
| FBC-B 404.5 SMOKE CONTROL. A SMOKE CONTROL SYSTEM SHALL |
| BE INSTALLED IN ACCORDANCE WITH SECTION 909 ALL OF THIS |
| SECTION!!! |
| 909.2 GENERAL DESIGN REQUIREMENTS. |
| 909.3 SPECIAL INSPECTION AND TEST REQUIREMENTS. |
| 909.4 ANALYSIS. |
| 909.4.1 STACK EFFECT |
| |
| 6) SHEET A-1.0 THE LOWER LEFT HAND CORNER OF THE SHEET |
| THIS APPEARS TO BE A DOOR SCHEDULE, THE LEFT HALF IS |
| CUT OFF. 107.2.1.3 ADDITIONAL INFORMATION ISREQUIRED. |
| ,2014 FBC-B TABLE 716.5 OPENING PROTECTIVES. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |