2016-08-03 17:27:49 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: |
| JOB ADDRESS: 1230 WELLINGTON ST. |
| DESCRIPTION: REMODEL-FILL IN OF CARPORT |
| MASTER PERMIT:16071244 |
| |
| 1. WHAT IS BEING DONE TO REPLACE THE LOST ILLUMINATION |
| IN THE EXISTING LIVING ROOM AFTER REMOVING THE CEILING |
| FIXTURE? |
| 2. FBC-ER3903.3/NEC 210.70(A)(2)(C): THERE HAS TO BE |
| LIGHTING FOR THE EXISTING STAIRS. IF THERE IS AN |
| ELEVATION CHANGE OF SIX STEPS OR GREATER AT THE |
| EXISTING STAIRS, A SWITCH IS REQUIRED AT THE TOP AND |
| BOTTOM OF STAIRS. |
| 3. FBC-RE3901/NEC 210.52(A): THERE ARE MANY WALLS |
| REQUIRING OUTLETS THROUGHOUT THE NEWLY CONSTRUCTED AREA |
| NOT MEETING THE MINIMUM REQUIREMENTS OF THE CODE. |
| 4. FBC-ER3901/NEC 210.52(C): HAS SPACING REQUIREMENTS |
| FOR THE OUTLETS ON THE KITCHEN COUNTERS WHICH ARE NOT |
| REFLECTED ON THE SUBMITTED DRAWING. |
| 5. FBC-RE3905.6.2/NEC 314.27(A) LUMINAIRE OUTLETS. |
| BOXES USED AT LUMINAIRE OR LAMPHOLDER OUTLETS IN A |
| CEILING SHALL BE REQUIRED TO SUPPORT A LUMINAIRE |
| WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE NOTES ON |
| CEILING BOXES ON PAGE. |
| 6. FBC-RE3902.12/NEC 210.12B - OUTLETS IN THE NEW |
| CONSTRUCTION SHALL BE AFCI PROTECTED. |
| 7. FBC-R4002.14 NEC 406.12 TAMPER-RESISTANT RECEPTACLES |
| IN DWELLING UNITS. IN ALL AREAS SPECIFIED IN 210.52, |
| ALL 125-VOLT, 15 AND 20 AMPERE RECEPTACLES SHALL BE |
| LISTED TAMPER RESISTANT RECEPTACLES. |
| 8. NEC 215.5: A RISER DIAGRAM SHOWING FEEDER DETAILS |
| ALONG WITH RESPECTIVE LOAD CALCS SHALL BE PROVIDED. |
| THIS DIAGRAM SHALL INCLUDE CONDUCTOR SIZING AND |
| INSULATION TYPE. FURTHERMORE, IT SHALL BE SITE |
| SPECIFIC. THE RISER DIAGRAM AS SUBMITTED DOES NOT |
| COMPLY AND THE LOAD CALCS DO NOT MATCH THE SUBMITTED |
| PANEL SCHEDULE. |
| 9. REVISE THE SUBMITTED PANEL SCHEDULE KVA & VOLTAGE |
| COLUMNS. |
| 10. THE NOTES ON THE PLAN REFER TO THE 150 AMP SERVICE |
| AS REQUIRED/PROVIDED. YOU SHALL INDICATE IF THE |
| EXISTING SERVICE IS A 150 AMP AND WILL REMAIN AS IS OR |
| IF ANY CHANGE BESIDES THE ADDITION OF THE REQUIRED |
| CIRCUITS IS TO BE PERFORMED. |
| 11. FBC-R314: YOU SHALL INSTALL SMOKE DETECTOR AS PER |
| CODE FOR NEW CONSTRUCTION. IF YOU HAVE GAS/FOSSIL FUEL |
| BURNING APPLIANCES OR AN ATTACHED GARAGE YOU SHALL ALSO |
| COMPLY WITH THE CARBON MONOXIDE REQUIREMENTS. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |