Plan Review Notes
Plan Review Notes For Permit 16071244
Permit Number 16071244
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-03 17:27:49ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 1230 WELLINGTON ST.
 DESCRIPTION: REMODEL-FILL IN OF CARPORT
 MASTER PERMIT:16071244
  
 1. WHAT IS BEING DONE TO REPLACE THE LOST ILLUMINATION
 IN THE EXISTING LIVING ROOM AFTER REMOVING THE CEILING
 FIXTURE?
 2. FBC-ER3903.3/NEC 210.70(A)(2)(C): THERE HAS TO BE
 LIGHTING FOR THE EXISTING STAIRS. IF THERE IS AN
 ELEVATION CHANGE OF SIX STEPS OR GREATER AT THE
 EXISTING STAIRS, A SWITCH IS REQUIRED AT THE TOP AND
 BOTTOM OF STAIRS.
 3. FBC-RE3901/NEC 210.52(A): THERE ARE MANY WALLS
 REQUIRING OUTLETS THROUGHOUT THE NEWLY CONSTRUCTED AREA
 NOT MEETING THE MINIMUM REQUIREMENTS OF THE CODE.
 4. FBC-ER3901/NEC 210.52(C): HAS SPACING REQUIREMENTS
 FOR THE OUTLETS ON THE KITCHEN COUNTERS WHICH ARE NOT
 REFLECTED ON THE SUBMITTED DRAWING.
 5. FBC-RE3905.6.2/NEC 314.27(A) LUMINAIRE OUTLETS.
 BOXES USED AT LUMINAIRE OR LAMPHOLDER OUTLETS IN A
 CEILING SHALL BE REQUIRED TO SUPPORT A LUMINAIRE
 WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE NOTES ON
 CEILING BOXES ON PAGE.
 6. FBC-RE3902.12/NEC 210.12B - OUTLETS IN THE NEW
 CONSTRUCTION SHALL BE AFCI PROTECTED.
 7. FBC-R4002.14 NEC 406.12 TAMPER-RESISTANT RECEPTACLES
 IN DWELLING UNITS. IN ALL AREAS SPECIFIED IN 210.52,
 ALL 125-VOLT, 15 AND 20 AMPERE RECEPTACLES SHALL BE
 LISTED TAMPER RESISTANT RECEPTACLES.
 8. NEC 215.5: A RISER DIAGRAM SHOWING FEEDER DETAILS
 ALONG WITH RESPECTIVE LOAD CALCS SHALL BE PROVIDED.
 THIS DIAGRAM SHALL INCLUDE CONDUCTOR SIZING AND
 INSULATION TYPE. FURTHERMORE, IT SHALL BE SITE
 SPECIFIC. THE RISER DIAGRAM AS SUBMITTED DOES NOT
 COMPLY AND THE LOAD CALCS DO NOT MATCH THE SUBMITTED
 PANEL SCHEDULE.
 9. REVISE THE SUBMITTED PANEL SCHEDULE KVA & VOLTAGE
 COLUMNS.
 10. THE NOTES ON THE PLAN REFER TO THE 150 AMP SERVICE
 AS REQUIRED/PROVIDED. YOU SHALL INDICATE IF THE
 EXISTING SERVICE IS A 150 AMP AND WILL REMAIN AS IS OR
 IF ANY CHANGE BESIDES THE ADDITION OF THE REQUIRED
 CIRCUITS IS TO BE PERFORMED.
 11. FBC-R314: YOU SHALL INSTALL SMOKE DETECTOR AS PER
 CODE FOR NEW CONSTRUCTION. IF YOU HAVE GAS/FOSSIL FUEL
 BURNING APPLIANCES OR AN ATTACHED GARAGE YOU SHALL ALSO
 COMPLY WITH THE CARBON MONOXIDE REQUIREMENTS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  