2016-09-08 17:46:46 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE EXISTING STRUCTURE WAS CONSTRUCTED IN 1950 AS AN |
| ATTACHED OPEN CARPORT. YOU ARE PROPOSING TO ENCLOSE THE |
| CARPORT AND CHANGE IT TO HABITABLE SPACE. THIS IS A |
| CHANGE OF OCCUPANCY WITH NO CHANGE OF OCCUPANCY |
| CLASSIFICATION. THE EXISTING STRUCTURE IS REQUIRED TO |
| BE EVALUATED FOR STRUCTURAL LOADS PER FBC EXISTING |
| BUILDING SECTION 1007. SUBMIT STRUCTURAL DRAWINGS THAT |
| SHOW THAT THE RENOVATED STRUCTURE WILL SAFELY SUPPORT |
| ALL LOADS, INCLUDING DEAD, LIVE LOADS, ROOF LOADS, WIND |
| LOADS, ETC. AND PROVIDE A CONTINUOUS LOAD PATH THAT |
| MEETS ALL THE REQUIREMENTS FOR THE TRANSFER OF ALL |
| LOADS FROM THEIR POINT OF ORIGIN THROUGH THE LOAD |
| RESISTING ELEMENTS TO THE FOUNDATION. FBC R301.1 |
| |
| 2) PROVIDE STRUCTURAL DETAILS OF THE EXISTING |
| STRUCTURE. SPECIFY THE RAFTER SIZE AND SPACING, THE |
| BEAM SIZES AND SPANS, THE COLUMN TYPE AND SPACING, AND |
| ALL CONNECTIONS. FBC 107.2.1 |
| |
| 3) SHOW THE LOCATION OF THE WATER HEATER ON THE |
| PROPOSED PLANS. FBCR P2801.1 |
| |
| 4) PROVIDE AREA TABULATIONS ON THE PLANS. FBC 107.2.1 |
| |
| 5) FBC 107.3.5.3 - PROVIDE WIND DESIGN DATA PURSUANT TO |
| FBC-R301.2 ON THE PLANS. |
| |
| 6) FBC 107.3.5.3 - INDICATE THE MEANS OF TERMITE |
| PROTECTION PROPOSED FOR THE ADDITION PURSUANT TO |
| FBC-R318. |
| |
| 7) FBC-R404.1.6 HEIGHT ABOVE FINISHED GRADE. CONCRETE |
| AND MASONRY FOUNDATION WALLS SHALL EXTEND ABOVE THE |
| FINISHED GRADE ADJACENT TO THE FOUNDATION AT ALL POINTS |
| A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY VENEER IS |
| USED AND A MINIMUM OF 6 INCHES (152 MM) ELSEWHERE. |
| PROVIDE TWO COPIES OF AN EXTERIOR WALL SECTION THAT |
| SHOWS THE EXTERIOR GRADE, THE FINISH FLOOR ELEVATION |
| AND THE CEILING ELEVATION. THE ELEVATION OF THE |
| CONCRETE SLAB ON GRADE WILL NEED TO BE 6" ABOVE THE |
| EXTERIOR FINISH GRADE. |
| |
| 8) R506.2.3 VAPOR RETARDER. A 6-MIL (0.006 INCH) |
| POLYETHYLENE OR APPROVED VAPOR RETARDER WITH JOINTS |
| LAPPED NOT LESS THAN 6 INCHES (152 MM) SHALL BE PLACED |
| BETWEEN THE CONCRETE FLOOR SLAB AND THE BASE COURSE OR |
| THE PREPARED SUBGRADE WHERE NO BASE COURSE EXISTS. |
| EXCEPTION: THE VAPOR RETARDER MAY BE OMITTED: 1. FROM |
| GARAGES, UTILITY BUILDINGS AND OTHER UNHEATED ACCESSORY |
| STRUCTURES. 2. FOR UNHEATED STORAGE ROOMS HAVING AN |
| AREA OF LESS THAN 70 SQUARE FEET (6.5 M2) AND CARPORTS. |
| 3. FROM DRIVEWAYS, WALKS, PATIOS AND OTHER FLATWORK NOT |
| LIKELY TO BE ENCLOSED AND HEATED AT A LATER DATE. 4. |
| WHERE APPROVED BY THE BUILDING OFFICIAL, BASED ON LOCAL |
| SITE CONDITIONS. |
| |
| 9) FBC-R704 INSPECTION FOR TERMITES IN ORDER TO PROVIDE |
| FOR INSPECTION FOR TERMITE INFESTATION, CLEARANCE |
| BETWEEN EXTERIOR WALL COVERINGS AND FINAL EARTH GRADE |
| ON THE EXTERIOR OF A BUILDING SHALL NOT BE LESS THAN 6 |
| INCHES (152 MM). |
| EXCEPTIONS: |
| 1. PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS THAN |
| 5/8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE |
| MASONRY FOUNDATION SIDEWALL. |
| 2. ACCESS OR VEHICLE RAMPS WHICH RISE TO THE INTERIOR |
| FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH RAMPS |
| ONLY. |
| 3. A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO AND |
| GARAGE SLABS AND ENTRY AREAS. |
| |
| 10) SECTION R317 PROTECTION OF WOOD AND WOOD BASED |
| PRODUCTS AGAINST DECAY |
| R317.1 LOCATION REQUIRED. PROTECTION OF WOOD AND WOOD |
| BASED PRODUCTS FROM DECAY SHALL BE PROVIDED IN THE |
| FOLLOWING LOCATIONS BY THE USE OF NATURALLY DURABLE |
| WOOD OR WOOD THAT IS PRESERVATIVE-TREATED IN ACCORDANCE |
| WITH AWPA U1. |
| 5. WOOD SIDING, SHEATHING AND WALL FRAMING ON THE |
| EXTERIOR OF A BUILDING HAVING A CLEARANCE OF LESS THAN |
| 6 INCHES (152 MM) FROM THE GROUND OR LESS THAN 2 INCHES |
| (51 MM) MEASURED VERTICALLY FROM CONCRETE STEPS, PORCH |
| SLABS, PATIO SLABS, AND SIMILAR HORIZONTAL SURFACES |
| EXPOSED TO THE WEATHER. |
| |
| 11) R806.1 VENTILATION REQUIRED. |
| ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL |
| HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM |
| AND 1/4 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS |
| HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM) |
| SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH |
| SCREENING, HARDWARE CLOTH, OR SIMILAR MATERIAL WITH |
| OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM) |
| MINIMUM AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF |
| FRAMING MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF |
| SECTION R802.1.8. REQUIRED VENTILATION OPENINGS SHALL |
| OPEN DIRECTLY TO THE OUTSIDE AIR. |
| |
| 12) THE PLANS SPECIFY R - 30 INSULATION IN THE CEILING. |
| VERIFY THAT THE EXISTING RAFTER SPACE WILL BE ADEQUATE |
| FOR THE INSULATION AND AIR SPACE. FBC 107.2.1 |
| |
| 13) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| |
| 14) THE FOUNDATIONS FOR OPEN CARPORTS SUCH AS THIS ARE |
| TYPICALLY ISOLATED PADS AT THE SUPPORT COLUMNS WITH A |
| 4" THICK SLAB ON GRADE. VERIFY THAT THE EXISTING SLAB |
| HAS A REINFORCED THICKENED EDGE. IF NOT YOU WILL NEED |
| TO INSTALL AN ADEQUATE FOOTING FOR THE EXTERIOR WALLS. |
| FBC R401.2 |
| |
| 15) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |