Plan Review Notes For Permit 16071222 |
Permit Number |
16071222 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-03 08:32:48 | ELECTRICAL REVIEW NOTES | | REVIEWED FOR COMPLIANCE WITH: | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | PROJECT NAME: JOSEPH WEINBERG | | JOB ADDRESS: 8744 LAKES BLVD. | | DESCRIPTION: INSTALLATION OF STAND-BY GENERATOR | | MASTER PERMIT:16071222 | | REVISION: | | | | PERMIT CONDITIONALLY APPROVED WITH THE FOLLOWING | | CORRECTIONS TO THE SUBMITTAL. ALL WORK IS SUBJECT TO | | FIELD INSPECTOR?S APPROVAL. | | 1. NEC 240.4(B): DUE TO THE OCPD INCORPORATED INTO THE | | GENERATOR OF 100 AMP #4 CU WILL NOT BE PROTECTED. | | 2. NEC 310.15(B): CONDUCTOR FOR 100 AMP IS #3CU (#4CU | | IS FOR 85 AMP) | | 3. NEC 240.6: THE NEXT STANDARD OCPD FOR #4 IS 90 AMP, | | NOT 100. | | 4. NEC 250.122: EQUIPMENT GROUNDING CONDUCTOR FOR 100 | | AMP IS #8. NOTHING SAYS YOU CANT USE #6. | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] | | |
|