Plan Review Notes
Plan Review Notes For Permit 16071217
Permit Number 16071217
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-01 14:35:01REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1) FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2) FBC-107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT
  
 3) NEC 215.5 PROVIDE A DIAGRAM SHOWING FEEDER ROUTING,
 SERVICE RISER DIAGRAM TO SHOW POWER SOURCE FROM UTILITY
 SERVICE.
  
 4) FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER
 OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
 OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR
 A MAXIMUM OF 3% VOLTAGE DROP.
  
 5) PROVIDE AIC RATING OF OCPD AND ELECTRICAL EQUIPMENT
 NEC 110.9 & 110.10, FPL LETTER MIGHT BE REQUIRED TO
 VERIFY AVAILABLE FAULT CURRENT NEC 110.24(A)
  
 6) OUTDOOR ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN
 SUITABLE ENCLOSURES AND SHALL BE PROTECTED FROM
 ACCIDENTAL CONTACT BY UNAUTHORIZED PERSONNEL, OR BY
 VEHICULAR TRAFFIC, OR BY ACCIDENTAL SPILLAGE OR LEAKAGE
 FROM PIPING SYSTEMS. IF APPLICABLE PLEASE PROVIDE
 PROPER GUARDING NEC 110.27
  
 ADDITIONAL COMMENTS MAY BE ADDED ON THE NEXT SUBMITTAL
 IF NECCESSARY.
  