Plan Review Notes
Plan Review Notes For Permit 16071174
Permit Number 16071174
Review Stop G
Sequence Number 1
Notes
Date Text
2016-07-29 06:39:09 
 1.) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 2.)THE GAS DRAWING SHOWS THE GAS PIPING ENTERING THE
 STRUCTURE. SUBMIT A GAS RISER SHOWING ALL GAS
 APPLIANCES ON THE SYSTEM, THE BTU LOAD OF EACH
 APPLIANCE AND THE LONGEST LENGTH OF PIPING FROM THE
 POINT OF DELIVERY TO THE MOST REMOTE OUTLET AND THE
 LOAD OF EACH SECTION.
  
 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (
 METER OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 5) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 6) INDICATE ON THE PLANS AND PERMIT APPLICATION IF THIS
 IS A NEW INSTALLATION OR IF IT IS REPLACING AN EXISTING
 TANKLESS WATER HEATER IN THE SAME LOCATION.
  
 7) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER IN RELATION TO
 ANY OPERABLE DOORS OR WINDOOWS. THE LOCATION OF THE
 WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS.
  
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  