Plan Review Notes For Permit 16071123 |
Permit Number |
16071123 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-07-30 03:02:20 | 1) SPECIFY WHAT THE AREA WITH THE LIGHT THAT IS | | ADJACENT TO THE SPA IS PROPOSED TO BE. WPB AMEND. TO | | FBC SEC. 107.2.1. | | 2) THE NOTES ON SHEET 2 OF 2 AT THE POOL & SPA PIPE | | SCHEMATIC ARE BECOMING DIFFICULT TO READ. PLEASE | | ADDRESS THIS COMMENT FOR FUTURE SUBMITTALS AND ENSURE | | THE NOTES ARE LEGIBLE. | | 3) A BACKFLOW PREVENTION DEVICE WILL BE REQUIRED ON THE | | WATER SERVICE. THIS SHALL BE DONE AS A SEPARATE PERMIT | | SUBMITTAL. | | 4) A TEST REPORT FROM AN INDEPENDENT LABORATORY IS | | REQUIRED TO VERIFY PROCEDURE COMPLIANCE OF THE HEAT | | PUMP WITH AHRI 1160 PER THE 2014 FBC-ENERGY | | SEC.R403.9.1.2. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|