2016-07-30 03:02:201) SPECIFY WHAT THE AREA WITH THE LIGHT THAT IS
 ADJACENT TO THE SPA IS PROPOSED TO BE. WPB AMEND. TO
 FBC SEC. 107.2.1.
 2) THE NOTES ON SHEET 2 OF 2 AT THE POOL & SPA PIPE
 SCHEMATIC ARE BECOMING DIFFICULT TO READ. PLEASE
 ADDRESS THIS COMMENT FOR FUTURE SUBMITTALS AND ENSURE
 THE NOTES ARE LEGIBLE.
 3) A BACKFLOW PREVENTION DEVICE WILL BE REQUIRED ON THE
 WATER SERVICE. THIS SHALL BE DONE AS A SEPARATE PERMIT
 SUBMITTAL.
 4) A TEST REPORT FROM AN INDEPENDENT LABORATORY IS
 REQUIRED TO VERIFY PROCEDURE COMPLIANCE OF THE HEAT
 PUMP WITH AHRI 1160 PER THE 2014 FBC-ENERGY
 SEC.R403.9.1.2.
  