Notes |
Date |
Text |
2016-07-29 17:49:49 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO SETS OF ELECTRICAL LOAD CALCULATIONS AND | | A PANEL SCHEDULE TO SHOW THAT THE EXISTING ELECTRICAL | | SYSTEM IS ADEQUATE TO ADD THE POOL HEATER AND | | EQUIPMENT. FBC 107.2.3 | | | | 2) SHOW COMPLIANCE WITH FBCR - E4204.3 FOR BONDING OF | | THE POOL WATER. |
|