2016-08-12 10:41:08 | FAILED |
| |
| 1) THE ARCHITECTURAL SITE PLAN INCORRECTLY SHOWS THE |
| CURRENT AND FUTURE LAYOUT OF THE ENTIRE WESTERN PARKING |
| AREA. PLEASE ENSURE THAT THE CORRECT EXISTING AND |
| APPROVED BASE INFORMATION IS USED ON THE ARCHITECTURAL |
| SITE PLANS. |
| |
| 2) RESOLUTION NO. 379-10 GOVERNS THE LIMITED STREET |
| CLOSURE OF COCOANUT AND TUXEDO LANES TO INCLUDE THE |
| TIMES THE CLOSURE IS PERMITTED, THE GATE PLACEMENT AND |
| PUBLIC ACCESS. |
| A. THE PROPOSED GATE BY AUSTIN LANE IS LOCATED OUTSIDE |
| OF THE LIMITED STREET CLOSURE AREA AND NOT AT THE |
| APPROVED GATE LOCATION. |
| B. THERE ARE ONLY TWO GATES PERMITTED, ONE AT EITHER |
| END OF THE LIMITED STREET CLOSURE AREA AND NOT WITHIN |
| THE STREET CLOSURE. THE GATE LOCATED ADJACENT TO THE |
| EAST END OF THE FIELD IS NOT PERMITTED AND SHALL BE |
| REMOVED FROM THE PLANS. |
| C. SECTION 3 OF RESOLUTION NO. 379-10 REQUIRES THAT |
| TUXEDO LANE AND COCOANUT LANE REMAIN OPEN TO PEDESTRIAN |
| AND BICYCLE TRAFFIC AT ALL TIMES. THE CURRENT GATE |
| LOCATIONS ALLOW PEDESTRIANS AND BICYCLISTS TO GO AROUND |
| THE GATES AND THUS MEET THIS REQUIREMENT. THE PROPOSED |
| GATE LOCATIONS SEEM TO BLOCK ACCESS. PLEASE PROVIDE |
| VERIFICATION THAT THE SECTION 3 REQUIREMENT CAN BE MET. |
| BLOW UP DETAILS AT THE GATES WOULD BE HELPFUL. |
| |
| 3) THE ARCHITECTURAL SITE PLAN REFERENCES NEW GATES AND |
| FENCING ON SHEET AS2.1. NO SHEET EXISTS. IS THIS |
| SUPPOSED TO BE SHEET G2.5? STAFF WILL REVIEW IF G2.5 IS |
| THE CORRECT SHEET. |
| |
| 4) PLEASE THE FOLLOWING INFORMATION ON FENCE C AND GATE |
| C2. |
| A. HOW TALL IS FENCE C. |
| B. FENCE C AND GATES C AND C2 ARE INDICATED AS |
| CONSTRUCTION RELATED. PLEASE NOTE THAT IN ACCORDANCE |
| WITH SECTION 94-450 TEMPORARY CONSTRUCTION FENCES MAY |
| ONLY BE ERECTED WHILE THERE IS AN ACTIVE BUILDING |
| PERMIT OPEN FOR THE PROPERTY. |
| C. TEMPORARY CONSTRUCTION FENCES AND GATES ARE REQUIRED |
| TO HAVE SCREENING THAT IS AT LEAST 85 PERCENT OPACITY. |
| PLEASE PROVIDE THE SCREENING DETAILS. |
| D. IF THE FENCE AND GATES ARE NOT TO BE CONSTRUCTION |
| FENCES, THEN THEY MAY HAVE NO SCREENING MATERIAL ON |
| THEM. |
| |
| 5) FENCES A AND D AND GATE A MEET ZONING REQUIREMENTS. |
| |
| 6) THE PBDA PLAT SHALL BE RECORDED PRIOR TO ISSUANCE OF |
| FINAL 104 INSPECTION APPOVAL. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| |
| |
| |