Plan Review Notes
Plan Review Notes For Permit 16071059
Permit Number 16071059
Review Stop M
Sequence Number 4
Notes
Date Text
2017-07-20 13:03:29MECHANICAL PROVISOS
 PERMIT #16071059
 BUILDING #2
 7/20/2017
  
 1) PROVIDE A ELECTRONICALLY SIGNED AND SEALED COVER
 SHEET AND INDEX FOR ALL THE OF AC SYSTEM SIZING
 CALCULATIONS.
  
 2) THE TRASH ROOM EXHAUST FAN CAPACITY MUST INCREASE TO
 PROVIDE A MINIMUM EXHAUST RATE OF 1.00 CFMS PER SQ. FT
 PER ASHRAE 62.1. PLEASE REVISE THE FAN SCHEDULE AND
 EXHAUST CALCULATIONS ON THE PLAN.
  