2017-05-31 11:55:07PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING
 1)
 PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING
 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4)
  
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION
 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE
 TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND
 IN SERVICE PRIOR TO CONSTRUCTION WORK.
  
 GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION
 TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241
 SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 REPEAT COMMENT - SHEET WS-2: NO FIRE DEPARTMENT
 CONNECTIONS PROVIDED FOR BUILDING #3 OR #4.
  
 REPEAT COMMENT - SHEET FA-1.00A: ALL OF THE CODES AND
 STANDARDS REFERENCED IN NOTE #34 ARE OUT OF DATE.
  
 DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ
 SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4).
  
 NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT.
 ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND
 PRIVATE UNDERGROUND FIRE MAINS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]