Date |
Text |
2016-08-29 09:41:37 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 |
| COMMENTS: |
| |
| 1. E1.00-1.01- GENERAL NOTES TO CONSTRUCTION DOCUMENTS: |
| PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| SUBMITTALS FOR ALL SITE LIGHTING AND ASSOCIATED |
| EQUIPMENT, ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT |
| LIMITED TO FIRE ALARM, ACCESS CONTROLS (GATES), CCTV, |
| PHONE AND DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL |
| SUFFICE. |
| 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3, |
| 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP |
| AND COMPLETIONS DOCUMENTS. |
| 3. E1.00- PROVIDE A NOTE TO POOL TO BE UNDER SEPARATE |
| PERMIT. |
| 4. E1.02- DELETE REFERENCE TO MIAMI DADE COUNTY |
| STANDARDS FOR LIGHTING ILLUMINATION PARKING AREA. |
| 5. PLEASE ADDRESS FIRE COMMENTS RELATED TO EM LIGHTING |
| REQUIREMENTS. |
| 6. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION |
| PROVIDED BY FPL UTILITY FOR APPROVAL. NEC 110.24 FBC |
| 107. |
| 7. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| VERBIAGE IN CODE. |
| 8. PLEASE CLARIFY FIRE PUMP REFERENCE ON RISER DIAGRAM |
| FOR A COMPLETE REVIEW. FBC 107.3.5 |
| 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| TO CONTACT ME SHOULD YOU HAVE ANY |
| |
| |
| VALENTINO PEREZ |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6717 |
| [email protected] |
| |
| |