Plan Review Notes
Plan Review Notes For Permit 16071058
Permit Number 16071058
Review Stop M
Sequence Number 3
Notes
Date Text
2017-07-14 15:45:033RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16071058
 BUILDING #3
 7/14/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER'S NARRATIVE AND THE CORRECTED PLANS
 HAVE ONLY ADDRESSED COMMENT #3 FROM THE 2ND REVIEW. I
 AM REPRINTING THE COMMENTS BELOW WITH COMMENT #3
 REMOVED- PLEASE COMPLY.
  
 2ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16071058
 6/8/17
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS- MISSING
 DOCUMENTS: THE SUBMITTED AC CALCULATION PACKET DOES NOT
 INCLUDE THE AHU-A2/CU-2, AHU-A3/CU-3, & AHU-B2/CU-2,
 SYSTEMS, AND ARE LISTING MIAMI AS THE LOCATION. A)
 REVIEW THE AC SCHEDULE ON M-4.00 AS THE 4-TON SYSTEM
 AHU-1 SYSTEM DOES NOT MATCH THE AHU-1 SYSTEM SHOWN ON
 SHEET M-2.00 IN TERMS OF CAPACITY. B)
  
 REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. A
 COOLING AND HEATING CALCULATION SHALL BE SUBMITTED FOR
 EACH SYSTEM SHOWN ON THE PLAN, AND ALL SUMMARY
 CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER SHALL
 BEAR THE SIGNATURE AND SEAL OF THE ENGINEER.
  
 2) SHEET M-2.00: THE DRYER EXHAUST DUCTS IN UNITS A1,
 A1 ACCESSIBLE, AND A3 ARE NOT PERMITTED TO RUN THROUGH
 THE MECHANICAL CLOSETS PER SECTION 504.4.
  
 4) MISSING DOCUMENTS: PROVIDE ENERGY COMPLIANCE FORM
 R405-2014 FOR UNIT A1, AND FOR ENTIRE BUILDING #3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  