Plan Review Notes
Plan Review Notes For Permit 16071058
Permit Number 16071058
Review Stop B
Sequence Number 3
Notes
Date Text
2017-07-12 12:49:48****CORRECTIONS****
 IF ALL OTHER TRADES PASS REVIEW, PLEASE CONTACT ME
 REGARDING A POSSIBLE PROVISO
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THIS PERMIT INCLUDES FOUR BUILDINGS:
  
 PERMIT #16070916 906 17TH STREET - 68 UNITS, 4 STORIES
 (BUILDING 1) THRESHOLD BUILDING
 PERMIT #16071059 808 17TH STREET - 45 UNITS, 3 STORIES
 (BUILDING 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 4)
  
 ALL FOUR BUILDINGS WILL BE REVIEWED UNDER THIS PERMIT
 NUMBER.
  
 COMMENTS FROM PREVIOUS REVIEW, NOT ADDRESSED:
  
 1-10. OK
  
 11. FS471, FBC CHAPTER 16, THE STRUCTURAL REPORT DATED
 8.10.2016 HAS AN INVALID DIGITAL SIGNATURE, HOWEVER, IT
 APPEARS THAT THE STRUCTURAL DESIGN HAS CHANGED. ALSO,
 THE STRUCTURAL REPORT PREVIOUSLY UPLOADED HAS ERRORS
 (FOR EXAMPLES SEE SHEETS 145, 146, "SHEAR STRESS DUE TO
 SHEAR FORCE AND TORSION TOGETHER EXCEEDS MAXIMUM
 ALLOWED").
  
 PROVIDE UPDATED REPORT CONSISTENT WITH NEW STRUCTURAL
 DESIGN, CONFIRM THERE ARE NO ERROR MESSAGES IN THE
 REPORT PRIOR TO SUBMITTAL, OR EXPLAIN WHY ANY ERROR
 MESSAGES ARE NOT RELEVANT.
  
 3RD REVIEW, THE SAME REPORT WAS PROVIDED (WITH A VALID
 SIGNATURE & SEAL). THEREFORE, THE SAME ERRORS ARE IN
 THE REPORT. THE STRUCTURAL DESIGN CHANGED AFTER THIS
 REPORT WAS PREPARED; IT APPEARS THAT A NEW REPORT IS
 REQUIRED. REPORT SHOWS AN 8" SLAB (SEE TABLE 2.2 SHELL
 SECTIONS SUMMARY), PLAN WAS REVISED TO 6". COLUMN AND
 FOOTING LOCATIONS AND SIZES WERE REVISED.
  
 12. FBC B 1803, FS471, PROVIDE THE SIGNED AND SEALED
 SOILS REPORT PREPARED BY ARDAMAN & ASSOCIATES 3/28/16.
  
 3RD REVIEW, THIS REPORT HAS BEEN UPLOADED TWICE BUT IS
 NOT DIGITALLY OR ELECTRONICALLY SIGNED AND SEALED. A
 PAPER ORIGINAL MAY BE SUBMITTED, OR A DIGITALLY OR
 ELECTRONICALLY SIGNED AND SEALED REPORT CAN BE UPLOADED
 TO PROJECTDOX.
  
 13. SEE PREVIOUS LIST REGARDING THE THREE TEST REPORTS
 REQUIRED FOR FLOORING UNDERLAYMENT. SHEET A6.11, 6.12
 (AND POSSIBLY OTHER PAGES) SPECS ARDEX SD-P AND QT-SCU
 UNDERLAYMENT. EITHER REMOVE THE NOTE OR PROVIDE THE
 THREE TEST REPORTS AT THIS TIME. IT IS RECOMMENDED THAT
 THE NOTE BE REMOVED BUT INCORPORATE THE REQUIREMENT FOR
 THE THREE TEST REPORTS TO BE SUBMITTED AND REVIEWED
 PRIOR TO INSTALLATION.
  
 3RD REVIEW, NOT ADDRESSED.
  
 14-17. OK
  
 18. SEE IMPACT FEE REVIEW.
  
 19-21. OK
  
 22-30. OK
  
 WOOD TRUSSES ARE PROPOSED OVER THE CONCRETE ROOF. FOR
 BUILDINGS 1 AND 2, WHICH ARE TYPE IIA BUILDINGS, REVISE
 PLAN TO SHOW COMPLIANCE WITH FBC B 603.
  
 31. THIS PERMIT WILL BE ISSUED WITH PROVISOS (DO NOT
 ADDRESS AT THIS TIME):
  
 A. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL,
 POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE
 SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING,
 TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS.
 SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED.
  
 B. WORK AREAS TO COMPLY WITH FBC ACCESSIBILITY (FBC A
 902.1 ADVISORY, ABA) PER ARCHITECT
  
 C. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207
 IS TO COMPLY WITH THE FOLLOWING:
  
 (1) FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED
 GYPSUM CEILING ASSEMBLY).
 (2) FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT
 A DROPPED GYPSUM CEILING ASSEMBLY).
 (3) FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25
 AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450
 REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E
 84 OR UL 723.
  
 TEST REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE
 SUBMITTED PRIOR TO INSTALLATION.
  
 D. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS
 AND CLADDING, FBC 1609. PRODUCT APPROVALS, REVIEWED BY
 DESIGNER OF RECORD, ARE TO BE SUBMITTED PRIOR TO
 INSTALLATION. COMPONENTS AND CLADDING ARE TO COMPLY
 WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE
 OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT
 APPROVALS PRIOR TO SUBMITTAL.
  
 E. A SEPARATE ROOF PERMIT IS REQUIRED. THE PRODUCT
 APPROVAL REVIEWED BY DOR IS TO BE SUBMITTED PRIOR TO
 INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE
 INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED.
  
 F. CIVIL PAGES WERE NOT REVIEWED BY BUILDING; PAVING
 WILL BE REVIEWED UNDER A SEPARATE PERMIT.
  
 G. FAIR HOUSING COMPLIANCE; SHEET A1.00 HAS A NOTE:
 1 BED 75 UNITS WITH TYPE B BATH
 2 BED 50 UNITS WITH ONE TYPE A AND ONE TYPE B PER FHA
  
 H. SHORING/RESHORE PLANS AND ENGINEERING REVIEWED BY
 CONTRACTOR AND SPECIAL INSPECTOR ARE TO BE SUBMITTED,
 REVIEWED AND ISSUED (AS A "SUBMITTAL" TO THE BUILDING
 DIVISION) PRIOR TO INSTALLATION. NO AFFECTED WORK TO
 COMMENCE WITHOUT THE SHORING/RESHORE ENGINEERING ON
 SITE, REVIEWED AND ISSUED BY BUILDING DIVISION.
  
 I. A CONSTRUCTION GUARDRAIL DETAIL, PREPARED BY A
 DESIGN PROFESSIONAL LICENSED UNDER FS471 OR FS481, IS
 REQUIRED TO BE SUBMITTED, REVIEWED, AND ISSUED BY THE
 CITY. SUBJECT TO FIELD INSPECTOR'S DISCRETION, THIS MAY
 BE ACCEPTED IN THE FIELD AT TIME OF INSPECTION.
  
 ******************************************
 BUILDING DATA FOR CO & REPORTING (INTERNAL USE ONLY)
  
 USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS
 SQUARE FEET - 4964
  
 CONSTRUCTION TYPE: 14-V-B - 5TH ED TYPE V-B
 UNITS: 6
 FLOORS: 1
 BEDROOMS: 8
 ROOMS: 22
 SQ FT LIVABLE: 4964
 SQ FT FOOTPRINT: 4964
 SQ FT ROOF: 4964
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 26
 PROP USE: APARTMENT
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS: 8
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  
  