2017-07-12 12:49:48 | ****CORRECTIONS**** |
| IF ALL OTHER TRADES PASS REVIEW, PLEASE CONTACT ME |
| REGARDING A POSSIBLE PROVISO |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| THIS PERMIT INCLUDES FOUR BUILDINGS: |
| |
| PERMIT #16070916 906 17TH STREET - 68 UNITS, 4 STORIES |
| (BUILDING 1) THRESHOLD BUILDING |
| PERMIT #16071059 808 17TH STREET - 45 UNITS, 3 STORIES |
| (BUILDING 2) |
| PERMIT #16071058 811 15TH STREET - 6 UNITS, 1 STORY |
| (BUILDING 3) |
| PERMIT #16070880 805 15TH STREET - 6 UNITS, 1 STORY |
| (BUILDING 4) |
| |
| ALL FOUR BUILDINGS WILL BE REVIEWED UNDER THIS PERMIT |
| NUMBER. |
| |
| COMMENTS FROM PREVIOUS REVIEW, NOT ADDRESSED: |
| |
| 1-10. OK |
| |
| 11. FS471, FBC CHAPTER 16, THE STRUCTURAL REPORT DATED |
| 8.10.2016 HAS AN INVALID DIGITAL SIGNATURE, HOWEVER, IT |
| APPEARS THAT THE STRUCTURAL DESIGN HAS CHANGED. ALSO, |
| THE STRUCTURAL REPORT PREVIOUSLY UPLOADED HAS ERRORS |
| (FOR EXAMPLES SEE SHEETS 145, 146, "SHEAR STRESS DUE TO |
| SHEAR FORCE AND TORSION TOGETHER EXCEEDS MAXIMUM |
| ALLOWED"). |
| |
| PROVIDE UPDATED REPORT CONSISTENT WITH NEW STRUCTURAL |
| DESIGN, CONFIRM THERE ARE NO ERROR MESSAGES IN THE |
| REPORT PRIOR TO SUBMITTAL, OR EXPLAIN WHY ANY ERROR |
| MESSAGES ARE NOT RELEVANT. |
| |
| 3RD REVIEW, THE SAME REPORT WAS PROVIDED (WITH A VALID |
| SIGNATURE & SEAL). THEREFORE, THE SAME ERRORS ARE IN |
| THE REPORT. THE STRUCTURAL DESIGN CHANGED AFTER THIS |
| REPORT WAS PREPARED; IT APPEARS THAT A NEW REPORT IS |
| REQUIRED. REPORT SHOWS AN 8" SLAB (SEE TABLE 2.2 SHELL |
| SECTIONS SUMMARY), PLAN WAS REVISED TO 6". COLUMN AND |
| FOOTING LOCATIONS AND SIZES WERE REVISED. |
| |
| 12. FBC B 1803, FS471, PROVIDE THE SIGNED AND SEALED |
| SOILS REPORT PREPARED BY ARDAMAN & ASSOCIATES 3/28/16. |
| |
| 3RD REVIEW, THIS REPORT HAS BEEN UPLOADED TWICE BUT IS |
| NOT DIGITALLY OR ELECTRONICALLY SIGNED AND SEALED. A |
| PAPER ORIGINAL MAY BE SUBMITTED, OR A DIGITALLY OR |
| ELECTRONICALLY SIGNED AND SEALED REPORT CAN BE UPLOADED |
| TO PROJECTDOX. |
| |
| 13. SEE PREVIOUS LIST REGARDING THE THREE TEST REPORTS |
| REQUIRED FOR FLOORING UNDERLAYMENT. SHEET A6.11, 6.12 |
| (AND POSSIBLY OTHER PAGES) SPECS ARDEX SD-P AND QT-SCU |
| UNDERLAYMENT. EITHER REMOVE THE NOTE OR PROVIDE THE |
| THREE TEST REPORTS AT THIS TIME. IT IS RECOMMENDED THAT |
| THE NOTE BE REMOVED BUT INCORPORATE THE REQUIREMENT FOR |
| THE THREE TEST REPORTS TO BE SUBMITTED AND REVIEWED |
| PRIOR TO INSTALLATION. |
| |
| 3RD REVIEW, NOT ADDRESSED. |
| |
| 14-17. OK |
| |
| 18. SEE IMPACT FEE REVIEW. |
| |
| 19-21. OK |
| |
| 22-30. OK |
| |
| WOOD TRUSSES ARE PROPOSED OVER THE CONCRETE ROOF. FOR |
| BUILDINGS 1 AND 2, WHICH ARE TYPE IIA BUILDINGS, REVISE |
| PLAN TO SHOW COMPLIANCE WITH FBC B 603. |
| |
| 31. THIS PERMIT WILL BE ISSUED WITH PROVISOS (DO NOT |
| ADDRESS AT THIS TIME): |
| |
| A. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL, |
| POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE |
| SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING, |
| TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS. |
| SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED. |
| |
| B. WORK AREAS TO COMPLY WITH FBC ACCESSIBILITY (FBC A |
| 902.1 ADVISORY, ABA) PER ARCHITECT |
| |
| C. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207 |
| IS TO COMPLY WITH THE FOLLOWING: |
| |
| (1) FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED |
| GYPSUM CEILING ASSEMBLY). |
| (2) FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT |
| A DROPPED GYPSUM CEILING ASSEMBLY). |
| (3) FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25 |
| AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450 |
| REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E |
| 84 OR UL 723. |
| |
| TEST REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE |
| SUBMITTED PRIOR TO INSTALLATION. |
| |
| D. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS |
| AND CLADDING, FBC 1609. PRODUCT APPROVALS, REVIEWED BY |
| DESIGNER OF RECORD, ARE TO BE SUBMITTED PRIOR TO |
| INSTALLATION. COMPONENTS AND CLADDING ARE TO COMPLY |
| WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE |
| OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT |
| APPROVALS PRIOR TO SUBMITTAL. |
| |
| E. A SEPARATE ROOF PERMIT IS REQUIRED. THE PRODUCT |
| APPROVAL REVIEWED BY DOR IS TO BE SUBMITTED PRIOR TO |
| INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE |
| INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED. |
| |
| F. CIVIL PAGES WERE NOT REVIEWED BY BUILDING; PAVING |
| WILL BE REVIEWED UNDER A SEPARATE PERMIT. |
| |
| G. FAIR HOUSING COMPLIANCE; SHEET A1.00 HAS A NOTE: |
| 1 BED 75 UNITS WITH TYPE B BATH |
| 2 BED 50 UNITS WITH ONE TYPE A AND ONE TYPE B PER FHA |
| |
| H. SHORING/RESHORE PLANS AND ENGINEERING REVIEWED BY |
| CONTRACTOR AND SPECIAL INSPECTOR ARE TO BE SUBMITTED, |
| REVIEWED AND ISSUED (AS A "SUBMITTAL" TO THE BUILDING |
| DIVISION) PRIOR TO INSTALLATION. NO AFFECTED WORK TO |
| COMMENCE WITHOUT THE SHORING/RESHORE ENGINEERING ON |
| SITE, REVIEWED AND ISSUED BY BUILDING DIVISION. |
| |
| I. A CONSTRUCTION GUARDRAIL DETAIL, PREPARED BY A |
| DESIGN PROFESSIONAL LICENSED UNDER FS471 OR FS481, IS |
| REQUIRED TO BE SUBMITTED, REVIEWED, AND ISSUED BY THE |
| CITY. SUBJECT TO FIELD INSPECTOR'S DISCRETION, THIS MAY |
| BE ACCEPTED IN THE FIELD AT TIME OF INSPECTION. |
| |
| ****************************************** |
| BUILDING DATA FOR CO & REPORTING (INTERNAL USE ONLY) |
| |
| USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS |
| SQUARE FEET - 4964 |
| |
| CONSTRUCTION TYPE: 14-V-B - 5TH ED TYPE V-B |
| UNITS: 6 |
| FLOORS: 1 |
| BEDROOMS: 8 |
| ROOMS: 22 |
| SQ FT LIVABLE: 4964 |
| SQ FT FOOTPRINT: 4964 |
| SQ FT ROOF: 4964 |
| |
| SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF |
| KNOWN): |
| SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): |
| XX.XX |
| SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: |
| XX.XX |
| OCC LOAD: 26 |
| PROP USE: APARTMENT |
| SPRINKLER SYS? Y |
| SPRK REQ'D? Y |
| BATHRMS: 8 |
| |
| BLDG CODE: FL 2014 |
| OCC CLASS: 5TH ED R-2 |
| |
| |