2017-06-08 07:27:272ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16071058
 6/8/17
  
 RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS- THE
 SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE THE
 AHU-A2/CU-2, AHU-A3/CU-3, & AHU-B2/CU-2, SYSTEMS, AND
 ARE LISTING MIAMI AS THE LOCATION. A) REVIEW THE AC
 SCHEDULE ON M-4.00 AS THE 4-TON SYSTEM AHU-1 SYSTEM
 DOES NOT MATCH THE AHU-1 SYSTEM SHOWN ON SHEET M-2.00
 IN TERMS OF CAPACITY. B)
  
 REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. A
 COOLING AND HEATING CALCULATION SHALL BE SUBMITTED FOR
 EACH SYSTEM SHOWN ON THE PLAN, AND ALL SUMMARY
 CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER SHALL
 BEAR THE SIGNATURE AND SEAL OF THE ENGINEER.
  
 2) SHEET M-2.00: THE DRYER EXHAUST DUCTS IN UNITS A1,
 A1 ACCESSIBLE, AND A3 ARE NOT PERMITTED TO RUN THROUGH
 THE MECHANICAL CLOSETS PER SECTION 504.4.
  
 3) M-2.01, UNIT B-1: AS PREVIOUSLY NOTED IN THE 1ST
 REVIEW DRYER BOOSTER FANS ARE NO LONGER PERMITTED BY
 CODE.
  
 4) PROVIDE ENERGY COMPLIANCE FORM R405-2014 FOR UNIT
 A1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  