Plan Review Notes For Permit 16071058 |
Permit Number |
16071058 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-06-08 07:27:27 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16071058 | | 6/8/17 | | | | RESULTS: DENIED. | | | | 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS- THE | | SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE THE | | AHU-A2/CU-2, AHU-A3/CU-3, & AHU-B2/CU-2, SYSTEMS, AND | | ARE LISTING MIAMI AS THE LOCATION. A) REVIEW THE AC | | SCHEDULE ON M-4.00 AS THE 4-TON SYSTEM AHU-1 SYSTEM | | DOES NOT MATCH THE AHU-1 SYSTEM SHOWN ON SHEET M-2.00 | | IN TERMS OF CAPACITY. B) | | | | REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. A | | COOLING AND HEATING CALCULATION SHALL BE SUBMITTED FOR | | EACH SYSTEM SHOWN ON THE PLAN, AND ALL SUMMARY | | CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER SHALL | | BEAR THE SIGNATURE AND SEAL OF THE ENGINEER. | | | | 2) SHEET M-2.00: THE DRYER EXHAUST DUCTS IN UNITS A1, | | A1 ACCESSIBLE, AND A3 ARE NOT PERMITTED TO RUN THROUGH | | THE MECHANICAL CLOSETS PER SECTION 504.4. | | | | 3) M-2.01, UNIT B-1: AS PREVIOUSLY NOTED IN THE 1ST | | REVIEW DRYER BOOSTER FANS ARE NO LONGER PERMITTED BY | | CODE. | | | | 4) PROVIDE ENERGY COMPLIANCE FORM R405-2014 FOR UNIT | | A1. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|