2017-06-23 09:54:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THIS PERMIT INCLUDES FOUR BUILDINGS:
  
 PERMIT #16070916 906 17TH STREET - 68 UNITS, 4 STORIES
 (BUILDING 1) THRESHOLD BUILDING
 PERMIT #16071059 808 17TH STREET - 45 UNITS, 3 STORIES
 (BUILDING 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 4)
  
 ALL FOUR BUILDINGS WILL BE REVIEWED UNDER THIS PERMIT
 NUMBER.
  
 1. FA1.00A (AND POSSIBLY OTHER PLACES) GOVERNING CODE
 IS INCORRECT, REVISE AND CHECK ALL SHEETS.
  
 2-9. OK
  
 10. REVISE PLAN TO ADDRESS PLUMBING ACCESSIBILITY
 COMMENTS WHICH ARE ALSO APPLICABLE FOR BUILDING REVIEW,
 FBC 5TH EDITION ACCESSIBILITY.
  
 11. FS471, FBC CHAPTER 16, THE STRUCTURAL REPORT DATED
 8.10.2016 HAS AN INVALID DIGITAL SIGNATURE, HOWEVER, IT
 APPEARS THAT THE STRUCTURAL DESIGN HAS CHANGED. ALSO,
 THE STRUCTURAL REPORT PREVIOUSLY UPLOADED HAS ERRORS
 (FOR EXAMPLES SEE SHEETS 145, 146, "SHEAR STRESS DUE TO
 SHEAR FORCE AND TORSION TOGETHER EXCEEDS MAXIMUM
 ALLOWED").
  
 PROVIDE UPDATED REPORT CONSISTENT WITH NEW STRUCTURAL
 DESIGN, CONFIRM THERE ARE NO ERROR MESSAGES IN THE
 REPORT PRIOR TO SUBMITTAL, OR EXPLAIN WHY ANY ERROR
 MESSAGES ARE NOT RELEVANT.
  
 12. FBC B 1803, FS471, PROVIDE THE SIGNED AND SEALED
 SOILS REPORT PREPARED BY ARDAMAN & ASSOCIATES 3/28/16.
  
 13. SEE PREVIOUS LIST REGARDING THE THREE TEST REPORTS
 REQUIRED FOR FLOORING UNDERLAYMENT. SHEET A6.11, 6.12
 (AND POSSIBLY OTHER PAGES) SPECS ARDEX SD-P AND QT-SCU
 UNDERLAYMENT. EITHER REMOVE THE NOTE OR PROVIDE THE
 THREE TEST REPORTS AT THIS TIME. IT IS RECOMMENDED THAT
 THE NOTE BE REMOVED BUT INCORPORATE THE REQUIREMENT FOR
 THE THREE TEST REPORTS TO BE SUBMITTED AND REVIEWED
 PRIOR TO INSTALLATION.
  
 14. OK
  
 16. 16070916 (BUILDING 1) IS A THRESHOLD BUILDING,
 FS553.79(7)(D). ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633.
  
 2ND REVIEW, ENGINEER'S RESPONSE IS THAT THIS IS ON
 SHEET S0, UNABLE TO LOCATE. PLEASE CLOUD ALL CHANGES
 FBC 107. THIS STATEMENT IS REQUIRED BY THE ARCHITECT
 AND BY THE ENGINEER FOR BUILDING 1.
  
 17. THRESHOLD INSPECTION PLAN REQUIRED, FS 553.79.
  
 RESPONSE STATES THIS IS ATTACHED, UNABLE TO LOCATE.
  
 18. SEE IMPACT FEE REVIEW.
  
 19. VALUE HAS BEEN ADJUSTED PER ICC TABLES, FBC 109.
 WHEN AVAILABLE, PROVIDE A COPY OF THE CONTRACT FOR THIS
 JOB VIA EMAIL OR AT TIME OF RESUBMITTAL.
  
 20. OK
  
 21. A8.00, CLUB ROOM DOORS TO HAVE PANIC OR FIRE EXIT
 HARDWARE, 1008.1.10. THE HARDWARE REQUIREMENT IS
 APPLICABLE FOR ALL DOORS IN THE MEANS OF EGRESS.
  
 2ND REVIEW, I WAS UNABLE TO LOCATE DOOR LABELS. SEE
 A8.00, ONLY ONE DOOR (6A) HAS PANIC HARDWARE NOTE 19,
 BUT CLUB ROOM IS ASSEMBLY OCCUPANCY AND HAS TWO EXITS
 (ONE DOUBLE DOOR, ONE SINGLE DOOR). REVISE AND CLARIFY.
  
 22-30. OK
  
 NEW COMMENTS:
  
 PROJECT DATA A0.01, TRAVEL DISTANCE FOR RESIDENTIAL
 SHOULD BE 250' MAX PER FBC B TABLE 1016.2; PLAN APPEARS
 TO COMPLY BUT PLEASE CORRECT THE TABLE (325' STATED AS
 MAX).
  
 WOOD TRUSSES ARE PROPOSED OVER THE CONCRETE ROOF. FOR
 BUILDINGS 1 AND 2, WHICH ARE TYPE IIA BUILDINGS, REVISE
 PLAN TO SHOW COMPLIANCE WITH FBC B 603.
  
 31. THIS PERMIT WILL BE ISSUED WITH PROVISOS (DO NOT
 ADDRESS AT THIS TIME):
  
 A. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL,
 POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE
 SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING,
 TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS.
 SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED.
  
 B. WORK AREAS TO COMPLY WITH FBC ACCESSIBILITY (FBC A
 902.1 ADVISORY, ABA) PER ARCHITECT
  
 C. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207
 IS TO COMPLY WITH THE FOLLOWING:
  
 (1) FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED
 GYPSUM CEILING ASSEMBLY).
 (2) FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT
 A DROPPED GYPSUM CEILING ASSEMBLY).
 (3) FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25
 AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450
 REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E
 84 OR UL 723.
  
 TEST REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE
 SUBMITTED PRIOR TO INSTALLATION.
  
 D. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS
 AND CLADDING, FBC 1609. PRODUCT APPROVALS, REVIEWED BY
 DESIGNER OF RECORD, ARE TO BE SUBMITTED PRIOR TO
 INSTALLATION. COMPONENTS AND CLADDING ARE TO COMPLY
 WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE
 OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT
 APPROVALS PRIOR TO SUBMITTAL.
  
 E. A SEPARATE ROOF PERMIT IS REQUIRED. THE PRODUCT
 APPROVAL REVIEWED BY DOR IS TO BE SUBMITTED PRIOR TO
 INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE
 INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED.
  
 F. CIVIL PAGES WERE NOT REVIEWED BY BUILDING; PAVING
 WILL BE REVIEWED UNDER A SEPARATE PERMIT.
  
 G. FAIR HOUSING COMPLIANCE; SHEET A1.00 HAS A NOTE:
 1 BED 75 UNITS WITH TYPE B BATH
 2 BED 50 UNITS WITH ONE TYPE A AND ONE TYPE B PER FHA
  
 H. SHORING/RESHORE PLANS AND ENGINEERING REVIEWED BY
 CONTRACTOR AND SPECIAL INSPECTOR ARE TO BE SUBMITTED,
 REVIEWED AND ISSUED (AS A "SUBMITTAL" TO THE BUILDING
 DIVISION) PRIOR TO INSTALLATION. NO AFFECTED WORK TO
 COMMENCE WITHOUT THE SHORING/RESHORE ENGINEERING ON
 SITE, REVIEWED AND ISSUED BY BUILDING DIVISION.
  
 I. A CONSTRUCTION GUARDRAIL DETAIL, PREPARED BY A
 DESIGN PROFESSIONAL LICENSED UNDER FS471 OR FS481, IS
 REQUIRED TO BE SUBMITTED, REVIEWED, AND ISSUED BY THE
 CITY. SUBJECT TO FIELD INSPECTOR'S DISCRETION, THIS MAY
 BE ACCEPTED IN THE FIELD AT TIME OF INSPECTION.
  
  
  
  
 ******************************
 INFORMATION FOR C.O.:
  
 16071058 BLDG 3
 USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS
 SQUARE FEET - 4964
  
 CONSTRUCTION TYPE: 14-V-B - 5TH ED TYPE V-B
 UNITS: 6
 FLOORS: 1
 BEDROOMS: 8
 ROOMS: 22
 SQ FT LIVABLE: 4964
 SQ FT FOOTPRINT: 4964
 SQ FT ROOF: 4964
  
 OCC LOAD: 26
 PROP USE: APARTMENT
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS: 8
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  