2016-09-24 09:18:23 | 1) SHT.A-0.01 - PROJECT DATA - THE PLAN REFERS TO THE |
| 2010 FBC. THE CODE IN EFFECT IS THE 5TH EDITION (2014) |
| VERSION OF THE FBC. REVISE THE NOTE. |
| 2) SHT. A0.01 - PROJECT DATA - COMPLIANCE NOTE - |
| FLORIDA DOES NOT ENFORCE THE ADA. FLORIDA HAS IT'S OWN |
| ACCESSIBILITY CODE UNDER THE 2014 FLORIDA BUILDING |
| CODE. REVISE THE NOTE TO READ 2014 FBC-ACCESSIBILITY |
| VOLUME. |
| 3) INDICATION THE DESIGN OPTION OF THE FAIR HOUSING ACT |
| (SPECIFICATION "A" OR SPECIFICATION "B" ) FOR THE |
| DWELLING UNITS. IF THERE IS A MIX OF SPECIFICATION A OR |
| B, INDICATE WHICH SPECIFICATION APPLIES TO WHICH UNITS. |
| WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| 4) THE W/S DRAWINGS HAVE NOT BEEN DIGITALLY SIGNED AND |
| SEALED AS REQUIRED BY FL. ADDMIN. CODE 61G15-23.001. |
| 5) SHT. A1.01 - DETAIL #1 SHOWS A DRAIN IN THE DUMPSTER |
| AREA. PROVIDE DETAILS AS TO THE TERMINATION POINT OF |
| THIS DRAIN. I DID NOT SEE ANY THING ON THE SITE |
| PLAN/CIVIL DRAWINGS FOR THIS DRAIN. |
| 6) SHT. A9.0 - DETAIL #1 - THE SIZING OF GUTTERS SHALL |
| COMPLY WITH 2014 FPC TABLE 1106.6. INDICATE THE SLOPE |
| OF THE GUTTERS AND THE SQUARE FOOTAGE OF THE ROOF |
| DRAINING INTO THE GUTTERS. |
| 7) SHT. A5.08 - ACCESSIBLE RESTROOM FIXTURE LEGEND - |
| THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 INCHES |
| FROM THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF |
| THE DISPENSER. FAC SEC. 604.7. |
| 8) SHT. A5.08 - SHOW THE DIMENSIONS (LXW) OF THE |
| REQUIRED CLEAR FLOOR SPACES FOR THE ACCESSIBLE |
| FIXTURES. COMPLY WITH FAC SECS. 305, 602, 604.3, 606.2, |
| 9) THE MAXIMUM DEPTH OF LAVATORY VANITIES IN THE |
| DWELLING UNITS SHALL BE 24 INCHES IN ACCORDANCE WITH |
| THE FHA GUIDELINES REQ. #7. SEE SHT. A6.14. |
| 10) SHT. A6.11 - DETAIL A & B - SHOW THE REQUIRED |
| CLEARANCE BETWEEN OPPOSING BASE CABINETS, COUNTERTOPS, |
| AND APPLIANCES PER REQUIREMENT #7 OF THE FHA |
| GUIDELINES. |
| 11) SHT. A6.15 - USABLE BATHROOM FIGURES - IDENTIFY |
| WHICH BATHROOMS ARE DESIGN SPECIFICATION A AND B. |
| 12) THE BUILDINGS HAVE TRASH ROOMS, MAINTENANCE ROOMS, |
| ETC. SANITARY FACILITIES FOR THE MAINTENANCE WORKERS |
| SHALL BE PROVIDED WITHIN 500 FEET OF THESE SPACES OF |
| THE BUILDINGS. 2014 FL. PLBG. CODE SEC.403.3.3. |
| 13) SHT. P1.00 SHOWS A 4 INCH DOMESTIC WATER SERVICE |
| LINE TO NOWHERE IN THE NE CORNER OF THE SHEET (BLDG. |
| #2) ? CLARIFY. |
| 14) THE PLUMBING SHEETS REFER TO CIVIL DRAWINGS FOR THE |
| CONTINUATION OF PLUMBING LINES. INDICATE THE SPECIFIC |
| CIVIL SHEET WHERE THE LINE CAN BE LOCATED. WPB AMEND. |
| TO FBC SEC. 107.2.1. |
| 15) THE PLUMBING PLANS REFER TO "SHEET DRAWINGS" FOR |
| THE CATCH BASINS. CLARIFY. |
| 16) THE POINT OF COMPASS ON THE PLUMBING DRAWINGS DOES |
| NOT INDICATE "NORTH", OR IT IS SO LIGHT ON THE PLANS |
| THAT A DETERMINATION CANNOT BE MADE. CLEARLY SHOW |
| "NORTH" ON THE PLANS.WPB AMEND, TO FBC SEC. 107.2.1. |
| 17) SHT. P-1.00 - IF POSSIBLE, IDENTIFY THE BUILDINGS |
| ON THE PLAN. WPB AMEND. TO FBC SEC. 107.2.1. |
| 18) SHT. P-2.00 - PROVIDE A REFERENCE NOTE LEGEND FOR |
| THIS PAGE AND ANY OTHER PAGES WHERE IT IS MISSING. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 19) SHT.P-2.00 - THERE ARE STORM DRAIN LINES, RAIN |
| WATER LEADER LINES, SANITARY LINES AND DOMESTIC WATER |
| LINES EXITING THE BUILDINGS WITH NO CONTINUATION POINT |
| SHOWN OR REFERENCED, PLEASE REFERENCE THE DRAWING |
| /SHEET NUMBER FOR CONTINUATION AND AVOID GENERAL NOTES |
| SUCH AS "SEE CIVIL DRAWINGS FOR CONTINUATION".WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 20) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION |
| MANUAL FOR THE OIL SMART PUMP SYSTEM IN THE ELEVATOR |
| SHAFT.WPB AMEND. TO FBC SEC. 107.2.1. |
| 21) THE HUB DRAINS FOR THE ELEVATOR SUMP DRAIN SHALL BE |
| EQUIPPED WITH TRAP PRIMERS PER THE 2014 FPC SEC.1002.4. |
| 22) SUBMIT CALCULATIONS AS TO HOW YOU ARRIVED AT THE |
| SIZE OF THE SCHIER LAUNDRY INTERCEPTOR.FPC SEC. 1003.2. |
| 23) SHT. P-2.05 REFERS TO AN ENLARGED FLOOR PLAN OF THE |
| LAUNDRY, RESTROOMS ETC. ON THE SAME SHEET. THERE IS NO |
| SUCH PLAN ON THE SHEET. REFER TO SHEET P-2.05 B. REVISE |
| NOTE TO REFER TO CORRECT SHEET. |
| 24) THE PLUMBING DRAWINGS SHOW STACKS IN THE WALLS WITH |
| IDENTIFICATION TAGS FOR THE RISERS BUT AN ARROW IS |
| INDICATING A DIFFERENT RISER THAN WHAT IS IDENTIFIED. |
| CLARIFY. |
| 25) SUBMIT A DETAIL OF THE DRYWELL.WPB AMEND. TO FBC |
| SEC. 107.2.1 |
| 26) ACCESS SHALL BE PROVIDED TO WATER SUPPLY VALVES FOR |
| THE STACKED WASHERS/DRYERS. 2014 FPC SEC.606.3. |
| 27) SHT. P-2.00 SHOWS RISER S/16 IN UNIT B1 ( #115 ) |
| BUT THIS RISER IS NOT ON THE COOLECTION SYSTEM ON |
| SHT.P-4.01 - CLARIFY. |
| 28) SHT. P-4.01 - RISER S/8 - UNIT A1 - (# 114 ) - |
| THERE ARE TWO RISERS WITH THE IDENTIFICATION TAG S/8 ON |
| THE COLLECTION ISOMETRIC BUT ONLY ONE S/8 RISER ON THE |
| PLAN VIEW ON SHT. P-2.00. CLARIFY. |
| 29) SHT. P-4.01 - THE ELEVATOR SUMP DRAINS ARE NOT |
| SHOWN ON THE COLLECTION ISOMETRIC. CLARIFY. |
| 30) SHT. P-4.03 - INDICATE THE RAINFALL RATE USED IN |
| SIZING THE STORM DRAIN SYSTEM.THE RAINFALL RATE USED |
| FOR THE SIZING OF THE SYSTEM SHALL BE 5 INCHES PERR |
| HOUR. 2014 FPC SEC.1106.1. |
| 31) INDICATE ON THE PLANS THE SLOPE OF THE PIPE FOR THE |
| STORM DRAINAGE SYSTEM. COMPLY WITH 2014 FPC SEC. 1106.2 |
| & 1106.3. |
| 32) SHT. P-4.05 - A URINAL IS NOT PERNITTED ON A WET |
| VENT PER FPC SEC. 912.1, 912.1.1. ONLY THE FIXTURES IN |
| THE BATHROOM GROUP ARE PERMITTED TO DISCHARGE INTO THE |
| WET VENT. REFER TO THE DEFINITION OF "BATHROOM GROUP" |
| IN THE DEFINITIONS (SEC. 202) OF THE 2014 FPC. |
| 33) SHT. P-2.05 B - THE MEN'S AND WOMEN'S RESTROOMS ARE |
| MISLABELED. |
| 34) THE LOCATION OF RISERS S/24 AND RISER S/25 ON SHT. |
| P2.05 B ARE REVERSED AS TO THE LAYOUT ON SHT. P-4.05. |
| SEE BUILDING #2 - UNIT B1 ( UNIT #115 ). |
| 35) SHT. P-4.05 - THE WASHING MACHINE STACKS SHALL BE A |
| MINIMUM OF 3 INCHES PER THE 2014 FPC SEC.406.2. |
| 36) SHT. P-4.05 - THE DRAINS FOR THE ELEVATOR SUMP ARE |
| NOT SHOWN ON THE RISER DIAGRAM. SHOW ALL PIPING ON THE |
| SANITARY RISER. WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| 37) THE LOCATION OF SANITARY RISERS S/24 AND S/25 ON |
| SHT.P-2.05 A DOES NOT CORRELATE WITH THE LOCATION OF |
| THE RISERS ON SHT. P-4.05. THE RISERS ARE REVERSED. THE |
| LOCATION OF RISER S/32 ON THE PLAN VIEW ON SHT.P-2.05 ( |
| A) DOES NOT CORRELATE WITH THE LOCATION ON THE SANITARY |
| COLLECTION ISOMETRIC ON SHT. P-4.05. |
| 38) SHT. P-4.05 - THERE ARE TWO SANITARY RISERS LABELED |
| S/23 AND ONLY ONE ON THE PLAN VIEW ON SHT,P-2.05 (A). |
| SEE UNIT B1 (#100). |
| 39) SHT. P-2.05 A - RISER S/22 IS SHOWN ON THE PLAN |
| VIEW BUT NOT ON THE SANITARY COLLECTION ISOMETRIC ON |
| SHT.P-4.05. REFER TO WALL BETWEEN UNIT B1 ( UNIT #100 ) |
| AND UNIT A1 ( UNIT # 101 ). THIS IS NOT MISLABELED AS |
| THERE IS A RISER S/23 FURTHER UPSTREAM. |
| 40) SHT. P- 5.00 - WASHING MACHINE BOX DETAIL - ACCESS |
| IS REQD. FOR THE UNION & REMOVEABLE TRAP SHOWN ON THE |
| DETAIL PER THE 2014 FPC SEC.405.8. |
| 41) SHT. P-5.00 - CHUTE DETAIL - A WATER HAMMER |
| ARRESTOR IS REQUIRED ON THIS WATER LINE FOR THE WASH |
| DOWN AS IT HAS A SOLENOID VALVE AND IS CCONSIDERED A |
| QUICK CLOSING VALVE. 2014 FPC SEC. 604.9. |
| |