2016-08-29 12:05:551ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16071058
 ROYAL PALM PLACE, BUILDING-3.
  
 1) THE SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE
 THE AHU-A2/CU-2, AHU-A3/CU-3, & AHU-B2/CU-2, SYSTEMS,
 AND ARE LISTING MIAMI AS THE LOCATION. A) REVIEW THE AC
 SCHEDULE ON M-4.00 AS THE 4-TON SYSTEM AHU-1 SYSTEM
 DOES NOT MATCH THE AHU-1 SYSTEM SHOWN ON SHEET M-2.00
 IN TERMS OF CAPACITY. B) REFER TO SECTION C403.2.1
 FBC-14 ENERGY
  
 CONSERVATION: A COOLING AND HEATING CALCULATION SHALL
 BE SUBMITTED FOR EACH SYSTEM SHOWN ON THE PLAN, AND ALL
 SUMMARY CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER
 SHALL BEAR THE SIGNATURE AND SEAL OF THE ENGINEER. SEE
 ALSO SECTION C407.5.2.3 IF SUBMITTING A TOTAL BUILDING
 PERFORMANCE ENERGY COMPLIANCE METHOD.
  
 2) SHEETS M-1.09, M-2.00, & M-400: THE SPLIT AC
 SCHEDULE DOES NOT INCLUDE THE AHU-2, AHU-3, AHU-B2, &
 AHU-B3 SYSTEMS.
  
 3) SHEETS M2.00 & M-2.01: THE EXCEPTION UNDER SECTION
 504.6.1 THAT ALLOWED THE USE OF DRYER BOOSTER FANS HAS
 BEEN REMOVED FROM THE FBC-14 MECHANICAL CODE. PLEASE
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND EXHAUST VENT
 INSTALLATION INSTRUCTIONS.
  
 4) THE PROPOSED BUILDING SHALL BE IN COMPLIANCE WITH
 THE FBC-14 ENERGY CONSERVATION CODE. REFER TO SECTIONS
 C101.2, C101.5, AND C401.2 AND SUBMIT COMPLIANCE
 MATERIALS AND FORMS.
  
 5) PROVIDE EQUIPMENT SCHEDULES FOR THE APARTMENT
 OUTSIDE AIR FANS AND MOTORIZED DAMPERS, AND PROVIDE
 CLEARANCE DISTANCE MEASUREMENTS FOR ALL AIR INTAKES-
 SECTION 401.4
  