2016-08-29 09:37:25INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. E1.00-1.01- GENERAL NOTES TO CONSTRUCTION DOCUMENTS:
 PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ALL SITE LIGHTING AND ASSOCIATED
 EQUIPMENT, ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT
 LIMITED TO FIRE ALARM, ACCESS CONTROLS (GATES), CCTV,
 PHONE AND DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL
 SUFFICE.
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP
 AND COMPLETIONS DOCUMENTS.
 3. E1.00- PROVIDE A NOTE TO POOL TO BE UNDER SEPARATE
 PERMIT.
 4. E1.02- DELETE REFERENCE TO MIAMI DADE COUNTY
 STANDARDS FOR LIGHTING ILLUMINATION PARKING AREA.
 5. PLEASE ADDRESS FIRE COMMENTS RELATED TO EM LIGHTING
 REQUIREMENTS.
 6. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION
 PROVIDED BY FPL UTILITY FOR APPROVAL. NEC 110.24 FBC
 107.
 7. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 8. PLEASE CLARIFY FIRE PUMP REFERENCE ON RISER DIAGRAM
 FOR A COMPLETE REVIEW. FBC 107.3.5
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  