2016-10-05 08:02:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THIS PERMIT INCLUDES FOUR BUILDINGS:
  
 PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING
 1)
 PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING
 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 4)
  
 ALL FOUR BUILDINGS WILL BE REVIEWED UNDER THIS PERMIT
 NUMBER.
  
 1. A0.01, FA1.00A (AND OTHER PLACES) GOVERNING CODE IS
 INCORRECT, REVISE AND CHECK ALL SHEETS.
  
 2. A0.01 INCLUDES ONLY R2 OCCUPANCY WHEN SHOWING
 COMPLIANCE WITH BUILDING HEIGHT AND AREA. REVISE PLAN
 TO INCLUDE THE BUSINESS AND ASSEMBLY OCCUPANCIES.
 REVISE PLAN TO SHOW COMPLIANCE WITH FBC TABLE 503.
  
 3. A0.01 FBC 508 BUILDING 2 IS A MIXED OCCUPANCY
 BUILDING. INDICATE WHETHER THIS IS SEPARATED OR NON
 SEPARATED MIXED USE.
  
 4. A0.01 TRAVEL DISTANCE DOES NOT INCLUDE ASSEMBLY
 OCCUPANCIES IN THE TABLE, REVISE, FBC 1016.
  
 5. COMPLIANCE WITH FBC 5TH EDITION ACCESSIBILITY, FAIR
 HOUSING IS NOT CLEAR. IF USING THE FAIR HOUSING DESIGN
 MANUAL, REVISE PLAN TO SHOW COMPLIANCE WITH
 SPECIFICATION A, SPECIFICATION B, NUMBER OF EACH.
  
 6. A1.00, COMPLIANCE WITH REQUIREMENTS FOR ACCESSIBLE
 PARKING SPACES IS NOT CLEAR. PLANS STATE COMPLIANCE
 WITH ADA, BUT DOES NOT COMPLY WITH THE PARKING REQUIRED
 BY FBC ACCESSIBILITY 208.2.
  
 REVISE PLAN TO CLEARLY INDICATE WHICH SPACES SERVE THE
 AMENITY, RESIDENTIAL, LEASING, AMENITY, EMPLOYEES.
 PROVIDE THE NUMBER FOR EACH AS WELL AS NUMBER OF
 ACCESSIBLE SPACES FOR THE SEPARATE USES. LEASING OFFICE
 TO COMPLY WITH ADA, RESIDENTIAL TO COMPLY WITH FHA
 UNLESS DESIGNER IS OPTING FOR ADA AS AN ALTERNATE
 DESIGN METHOD (IN WHICH CASE, NOT ENOUGH ACCESSIBLE
 PARKING IS PROVIDED). AT THIS POINT IT IS DIFFICULT TO
 DETERMINE REQUIREMENTS DUE TO LACK OF FAIR HOUSING
 INFORMATION.
  
 7. GENERAL COMMENT RE WORK AREAS, FBC ACCESSIBILITY
 902.1 ADVISORY, ABA ALSO APPLIES TO FACILITIES
 DESIGNED, BUILT, ALTERED, OR LEASED WITH FEDERAL FUNDS.
 EITHER CONFIRM COMPLIANCE OR CONFIRM NO FEDERAL FUNDS
 WERE USED. THIS MAY BE ADDRESSED IN THE RESPONSE
 LETTER.
  
 8. S0 HAS TEXT WHICH IS ILLEGIBLE (DESIGN CRITERIA),
 REVISE.
  
 9. SB3 2.1 IS NAMED CORRECTLY (ROOF) BUT THE DETAIL IS
 LABLED GROUND FLOOR FRAMING PLAN, REVISE, FBC 107.
  
 10. REVISE PLAN TO ADDRESS PLUMBING ACCESSIBILITY
 COMMENTS WHICH ARE ALSO APPLICABLE FOR BUILDING REVIEW,
 FBC 5TH EDITION ACCESSIBILITY.
  
 11. FS471, FBC 1609, THE STRUCTURAL REPORT DATED
 8.10.2016 HAS AN INVALID DIGITAL SIGNATURE, UPLOAD A
 CORRECTLY SIGNED AND SEALED REPORT.
  
 12. FBC 1803, PROVIDE THE SIGNED AND SEALED SOILS
 REPORT PREPARED BY ARDAMAN & ASSOCIATES 3/28/16. IT IS
 INCLUDED IN THE STRUCTURAL REPORT BUT THE SOILS REPORT
 NEEDS TO BE SIGNED AND SEALED BY THE ENGINEER ON THE
 SOILS REPORT TITLE BLOCK, FS 471.
  
 13. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207
 IS TO COMPLY WITH THE FOLLOWING:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED
 GYPSUM CEILING ASSEMBLY).
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT
 A DROPPED GYPSUM CEILING ASSEMBLY).
  
 C. FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25
 AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450
 REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E
 84 OR UL 723.
  
 THIS MAY BE A DEFERRED SUBMITTAL UPON REQUEST. TEST
 REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE
 SUBMITTED AS A REVISION PRIOR TO INSTALLATION.
  
 14. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS
 AND CLADDING, FBC 1609. THIS MAY BE A DEFERRED
 SUBMITTAL UPON REQUEST. PRODUCT APPROVALS, REVIEWED BY
 DESIGNER OF RECORD, ARE TO BE SUBMITTED AS A REVISION
 PRIOR TO INSTALLATION. COMPONENTS AND CLADDING ARE TO
 COMPLY WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE
 OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT
 APPROVALS PRIOR TO SUBMITTAL.
  
 15. A SEPARATE ROOF PERMIT IS REQUIRED. IF THIS
 SUBMITTAL IS DEFERRED, THE PRODUCT APPROVAL REVIEWED BY
 DOR IS TO BE SUBMITTED AS A REVISION PRIOR TO
 INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE
 INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED.
  
 16. 16070916 (BUILDING 1) IS A THRESHOLD BUILDING,
 FS553.79(7)(D). ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633.
  
 CONFIRM ALL APPLICABLE PAGES INCLUDE THE REQUIRED
 STATEMENT.
  
 17. THRESHOLD INSPECTION PLAN REQUIRED, FS 553.79.
  
 18. SEE IMPACT FEE REVIEW.
  
 19. VALUE HAS BEEN ADJUSTED PER ICC TABLES, FBC 109.
 WHEN AVAILABLE, PROVIDE A COPY OF THE CONTRACT FOR THIS
 JOB VIA EMAIL OR AT TIME OF RESUBMITTAL.
  
 20. FBC 107, FOR INFORMATION REQUIRED FOR C.O., PROVIDE
 A TOTAL PER BUILDING:
  
 ROOMS
 BATHROOMS
 BEDROOMS
  
 21. A8.00, CLUB ROOM DOORS TO SWING IN THE DIRECTION OF
 EGRESS TRAVEL AND TO HAVE PANIC OR FIRE EXIT HARDWARE,
 1008.1.10. THE HARDWARE REQUIREMENT IS APPLICABLE FOR
 ALL DOORS IN THE MEANS OF EGRESS. REVISE DOOR SCHEDULE
 TO CLARIFY.
  
 22. FBC 603, BUILDINGS 1 AND 2, IT IS NOT CLEAR UNDER
 WHAT EXEMPTION THE COMBUSTBLE OUTLOOKERS ARE PROPOSED,
 A3.00 AND OTHER SHEETS. SEE ALSO FBC 1406.
  
 23. FBC 603, SHEETS A3.00, 3.01, BUILDINGS 1 AND 2, FBC
 603.1(3), NOTE COMPLIANCE WITH REQUIREMENTS FOR FOAM
 PLASTICS FOR THE FOAM COLUMNS (OR REVISE PLAN TO SHOW
 APPLICABLE EXEMPTION).
  
 24. A2.05, THE WALL BETWEEN UNIT AND AMENITIES LACK THE
 WALL TAG, FBC 107.
  
 A0.01 INDICATES THAT BUILDINGS 3 AND 4 WILL BE
 SPRINKLERED, BUT I WAS UNABLE TO LOCATE FIRE SPRINKLER
 PLANS FOR THESE BUILDINGS, FBC 107, 903.2.8.
  
 25. S 0, WIND DESIGN CRITERIA INCLUDES HVHZ. THIS
 PROJECT IS NOT LOCATED IN HIGH VELOCITY, REMOVE NOTE.
 PLEASE NOTE THAT HIGH VELOCITY IS NOT MORE STRINGENT
 THAN NON HVHZ IN ALL CASES. THE MINIMUM REQUIREMENTS OF
 THE FBC NON HVHZ ARE TO BE MET OR EXCEEDED.
  
 26. ENERGY CALCS REQUIRED FBC 5TH EDITION ENERGY
 CONSERVATION C103 (BUILDING 1), R103 (BUILDINGS 2, 3,
 4).
  
 27. A1.00, LEGEND 10 REFERS TO THE WRONG BUILDING CODE
 AND ALSO REFERS TO ASCE 7 10. CLARIFY; IS THE POOL
 FENCE TO RESIST WIND LOADS? IF SO, WHAT WIND LOADS?
  
 28. A1.00, FBC 107, FBC 1004, OCCUPANT LOAD NOT SHOWN
 FOR THE POOL DECK AREA. FBC TABLE 1004, POOL DECK IS TO
 BE CALCULATED AT 15 SF PER PERSON, POOL SURFACE AT 50
 SF. IT APPEARS THAT THE OCCUPANT LOAD WILL EXCEED 50.
  
 29. A1.00, POOL GATES ARE TO COMPLY WITH THE
 REQUIREMENTS FOR DOORS, FBC 1008.2. THE FOLLOWING IS
 REQUIRED:
 SWING IN THE DIRECTION OF EGRESS TRAVEL
 INCLUDE PANIC OR FIRE EXIT HARDWARE
 SWING AWAY FROM THE POOL AND COMPLY WITH ALL
 REQUIREMENTS OF FBC 454.2.17.1.8
 THE TWO PAIRS OF GATES ARE NOT REMOTELY LOCATED AS
 REQUIRED BY
  
 30. CLARIFY DOOR AND GATE OBSTRUCTION INTO THE EGRESS
 PATH BETWEEN THE FOOD PREP ROOM AND POOL DECK, FBC 107.
  
 31. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL,
 POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE
 SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING,
 TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS.
 SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED.
  