Plan Review Notes
Plan Review Notes For Permit 16071055
Permit Number 16071055
Review Stop P
Sequence Number 1
Notes
Date Text
2016-08-13 03:42:041) DEFINE THE OCCUPANCY OF THE REAR STRUCTURE IN
 ACCORDANCE WITH THE FBC CHAPTER 3. THIS IS NOT AN R-2
 OCCUPANCY, THERE IS EXERCISE EQUIPMENT IN THIS
 BUILDING.THIS IS A CHANGE OF OCCUPANCY FROM A
 RESIDENTIAL USE AND FULL COMPLIANCE WITH THE 2014 FBC-
 ACCESSIBILITY IS REQD. PER 2014 FBC-EXISTING BUILDING
 CODE SEC.1012.1.4, 1012.8.
 2) THE BATHING ROOM IN THE REAR STRUCTURE SHALL COMPLY
 WITH THE 2014 FAC SEC.604 FOR LOCATION AND REQUIRED
 CLEARANCE FOR THE WATER CLOSET,SEE SEC. 606 FOR THE
 LAVATORY, SEC. 608 FOR THE SHOWER, GRAB BARS AND
 CONTROLS.
 3) A DRINKING FOUNTAIN (MINIMUM OF TWO) IS REQUIRED IN
 THE REAR STRUCTURE PER 2014 FBC-PLUMBING, TABLE 403.1
 AND FAC SEC. 211.
 4) THE SINK IN THE GYM SHALL COMPLY WITH FAC SECS.212 &
 606.
 5) IF THE 3-STORY IS DEEMED AN R-2 OCCUPANCY, THEN A
 WASHING MACHINE CONNECTION IS REQUIRED IN THE BUILDING
 PER FPC TABLE 403.1.
 6) THE KITCHEN SINK IN THE HANDICAPPED ACCESSIBLE
 SLEEPING ROOM IN THE 3 STORY SHALL CCOMPLY WITH FAC
 SEC.606, 809.3.. A SIDE APPROACH IS NOT PERMITTED
 UNLESS ALL THE REQUIREMENTS OF SEC.606.2 (3) (A-C) OF
 THE FAC IS MET. PROVIDE VERIFICATION THAT THE KITCHEN
 COMPLIES WITH THE EXCEPTION.
 7) THE BATHROOM IN THE HANDICAPPED ACCESSIBLE UNIT
 SHALL COMPLY WITH FAC SECS. 809.4, 603 THROUGH 610.
 8) SHT. S-6, DETAIL #03 - THE WATER CLOSET SHALL BE
 LOCATED A MINIMUM OF 15 INCHES FROM AN ADJACENT WALL
 PER 2014 FPC SEC.405.3.1.
 9) SHT. S-6, DETAIL 01 - THE RANGE /COOKTOP SHALL
 COMPLY WITH 2014 FAC SEC. 804.6.4. THE OVEN SHALL
 CCOMPLY WITH FAC SEC. 804.6.5.
 10) THE REFRRIGERATOR/FREEZER IN THE ACCESSIBLE UNIT
 SHALL COMPLY WITH FAC SEC. 804.6.6.
 11) A 30 INCH BY 60 INCH CLEARANCE SHALL BE PROVIDED
 ADJACENT TO THE OPEN FACE OF THE SHOWER IN THE
 ACCESSIBLE SHOWER COMPLYING WITH FAC SEC.608.2.2.1.
 12) THE LOCATION OF THE ACCESSIBLE SHOWER CONTROLS
 SHALL COMPLY WITH FAC SEC.608.5.2.
 13) THE GRAB BARS IN THE ACCESSIBLE SHOWER SHALL BE
 LOCATED IN ACCORDANCE WITH THE FAC SEC. 608.3.2.
 14) A SHOWER SPRAY UNIT SHALL BE PROVIDED IN THE
 ACCESSIBLE SHOWER AND COMPLY WITH FAC SEC.608.6.
 15) SHT. S-6 - THE DETAILS FOR THE ADA SHOWER /MOUNTING
 HEIGHTS IS FROM AN OUTDATED EDITION OF THE FLORIDA
 ACCESSIBILITY CODE. COMPLY WITH THE 2014 EDITION OF
 FAC.
 16) SHT. S-6 - SUBMIT AN EXPANDED SANITARY RISER FOR
 REVIEW.IT IS EXTREMELY DIFFICULT TO PERFORM A
 COMPREHENSIVE ON THE SANITARY RISER THAT HAS BEEN
 SUBMITTED. WPB AMEND. TO FBC SEC. 107.2.1.
 17) SUBMIT A WATER RISER DETAIL FOR CHANGES MADE TO THE
 EXISTING WATER SYSTEM. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 18) SHT. S-11 - THE SINK IN THE DETACHED STRUCTURE IS
 NOT PERMITTED ON A WET VENT PER 2014 FPC SEC.912.1.
 19) SIZE ALL THE VENTS ON THE SANITARY RISER FOR THE 3
 STORY STRUCTURE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805 PLUMBING PLAN REVIEW
 -6692
 [email protected]
  