2016-08-10 11:48:381ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16071074
 8/10/16
  
 1) IT IS NECESSARY THAT THE DESIGN PROFESSIONALS REVISE
 THE PLANS IN ACCORDANCE WITH THE BUILDING REVIEW
 COMMENTS BEFORE A THOROUGH MECHANICAL REVIEW CAN BE
 ACCOMPLISHED. BASED ON ALL THE DEFCIENCES IN THE PLAN
 CITED IN THE BUILDING COMMENTS, THIS REVIEW WILL BE
 CONSIDERED A PRELIMINARY REVIEW AND ADDITIONAL COMMENTS
 MAY OCCUR AFTER CORRECTED PLANS HAVE BEEN RESUBMITTED.
  
 2) THE SUBMITTED PLANS ARE INDICATING THIS IS A 3-STORY
 MULTI-FAMILY BUILDING- PLEASE CORRECT THE APPLICATION
 INDICATING A 2-STORY BUILDING.
  
 2) REGARDING THE ENERGY AND AC CALCULATION SUBMITTALS,
 PLEASE SEE SECTION R103.1.1.1.2 EXCEPTION FBC-14 ENERGY
 CONSERVATION, AND PROVIDE DOCUMENTATION OF ENERGY RATER
 CERTIFICATION FOR CONNIE'S E-CALCS.
  
 3) THE ENERGY CALCULATION FORM R405-2014 MUST BE SIGNED
 AND DATED BY THE OWNER/AGENT- SEE SECTION R103.1.1.2.
  
 4) THE SUBMITTED FORM R405-2014 INDICATES R30
 INSULATION UNDER THE ATTIC, AND R11 IN THE EXTERIOR
 WALLS- PLEASE PROVIDE SECTION CUTS FOR THE EXTERIOR
 WALLS AND ATTIC THAT SHOW THE INSULATION THICKNESSES
 AND R-VALUES. PLEASE NOTE THAT THE ENERGY CALCULATIONS
 ARE INDICATING 1246 SQ. FT. OF R30 INSULATION UNDER
 ATTIC. HOW WILL THIS BE ACCOMPLISHED WITH THE ATTIC
 APARTMENT THERE?
  
 5) SHEET M-1: INDICATE HOW VENTILATION OF ALL ROOMS AND
 SPACES WILL BE ACCOMPLISHED, EITHER NATURALLY OR
 MECHANICALLY AND PROVIDE CALCULATIONS- SEE SECTIONS
 401.2, 402.1, 402.2, AND TABLE 403.3 FBC-14 MECHANICAL.
  
 6) M-1: CU-5 IS SHOWN IN THE EQUIPMENT SCHEDULE AND IN
 THE PLANS FOR THE REAR BUILDING, HOWEVER IT IS NOT
 INCLUDED IN THE ENERGY OR AC CALCULATIONS. IS THIS
 BUILDING AND AC SYSTEM TO BE INCLUDED IN THIS PERMIT OR
 UNDER SEPARATE PERMIT?- PLEASE CLARIFY.
  
 7) M-1: SHOW THE CONDENSATE DISPOSAL PIPING RUNS AND
 INDICATE THE TYPE AND DIAMETER OF PIPING.
  
 8) M-1: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE CU'S- SECTIONS 301.15 MECHANICAL,
 AND SECTION 1609 FBC-14 BUILDING- BASIC WIND SPEED,
 IMPORTANCE FACTOR, EXPOSURE CATEGORY, HEIGHT AND
 ADJUSTMENT COEFFICIENT.
  
 9) SUBMIT AHRI CERTIFICATES FOR THEDAIKIN SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719