Date |
Text |
2016-07-28 14:03:12 | 1626 OKEECHOBEE ROAD |
| PERMIT #16071055 & 16071074 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY |
| REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE |
| (2012 EDITION WITH FLORIDA AMENDMENTS.) |
| |
| PLANS NEED TO BE SUBMITTED FOR A CHANGE OF OCCUPANCY |
| FROM AN APARTMENT BUILDING TO A RESIDENTIAL BOARD & |
| CARE FACILITY OR LODGING & ROOMING HOUSE. PER SECTION |
| 3.3.165 LODGING & ROOMING HOUSE. A BUILDING OR PORTION |
| THEREOF THAT DOES NOT QUALIFY AS A ONE- OR TWO-FAMILY |
| DWELLING, THAT PROVIDES SLEEPING ACCOMMODATIONS FOR A |
| TOTAL OF 16 OR FEWER PEOPLE ON A TRANSIENT OR PERMANENT |
| BASIS, WITHOUT PERSONAL CARE SERVICES, WITH OR WITHOUT |
| MEALS, BUT WITHOUT SEPARATE COOKING FACILITIES FOR |
| INDIVIDUAL OCCUPANTS. PER SECTION 3.3.188.12 |
| RESIDENTIAL BOARD AND CARE OCCUPANCY. AN OCCUPANCY USED |
| FOR LODGING AND BOARDING OF FOUR OR MORE RESIDENTS, NOT |
| RELATED BY BLOOD OR MARRIAGE TO THE OWNERS OR |
| OPERATORS, FOR THE PURPOSE OF PROVIDING PERSONAL CARE |
| SERVICES. |
| |
| PROVIDE A DETAILED LIFE SAFETY PLAN SHOWING ALL |
| OCCUPANCY TYPES, OCCUPANT LOADS, FIRE RATED WALLS, |
| EXITS, EXIT SIGNS, EMERGENCY LIGHTING, TRAVEL |
| DISTANCES, COMMON PATH OF TRAVEL, ESCAPE WINDOWS, DOOR |
| SCHEDULE, ETC. |
| |
| ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION |
| DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT. |
| AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE |
| SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS |
| (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) |
| FOR A SUB-PERMIT. |
| |
| PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| WWW.KNOXBOX.COM. |
| |
| STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| ADMINISTRATIVE CODE 69A-60.0081. |
| |
| NO STAIR OR HANDRAIL DETAILS SUBMITTED. |
| |
| DOOR LEAF ENCROACHMENT - DURING ITS SWING, ANY DOOR |
| LEAF IN A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN |
| ONE-HALF OF THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, |
| A PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL |
| PROJECT NOT MORE THAN 7-INCHES INTO THE REQUIRED WIDTH |
| OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING, |
| WHEN FULLY OPEN. |
| |
| A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED |
| AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON |
| THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED DURING PLAN RESUBMISSION. |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| FIRE INVESTIGATOR & INSPECTOR |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| |
| |
| |
| |