2016-08-03 09:24:27 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16071055/ 2 STORY/ R2/ |
| ADD: 1626 OKECHOBEE RD. |
| CONT: POTTSWORK CONSTRUCTION |
| TEL: 561-584-2563 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. AUG. 03/ 2016 |
| ACTION: DENIED |
| |
| 1) SHEET S-1 LISTS UNDER THE SCOPE OF WORK THIS PROJECT |
| AS A LEVEL III ALTERATION TO EXISTING 6 UNIT APARTMENTS |
| (R2 OCCUPANCY GROUP). THE COVER SHEET INDICATES THE |
| USAGE THE PROGRAM AS COMPREHENSIVE ALCOHOLISM |
| REHABILITATION PROGRAMS, INC. PLEASE NOTE THIS IS A |
| CHANGE OF USE WITHIN THE SAME OCCUPANCY GROUP OR |
| POSSIBLY FROM A R2 TO AN R4 (ALCOHOL & DRUG CENTERS, |
| ASSISTED LIVING FACILITIES AND OR RESIDENTIAL BOARD AND |
| CUSTODIAL CARE FACILITIES). |
| 2014 EXIST. BUILD. CODE 1001.3 CHANGE OF OCCUPANCY |
| CLASSIFICATION. |
| WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012 |
| SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| GROUP. PLEASE DECLARE THE END USAGE OF THE STRUCTURE, |
| THE OCCUPANT LOAD ( BEDS FOR THE TENANTS. A R-4 |
| CLASSIFICATION SHALL INCLUDE BUILDINGS, STRUCTURES OR |
| PORTIONS THEREOF FOR MORE THAN FIVE BUT NOT MORE THAN |
| 16 PERSONS, EXCLUDING STAFF, WHO RESIDE ON A 24-HOUR |
| BASIS IN A SUPERVISED RESIDENTIAL ENVIRONMENT AND |
| RECEIVE CUSTODIAL CARE. THE PERSONS RECEIVING CARE ARE |
| CAPABLE OF SELF-PRESERVATION. PLEASE NOTE IF THE |
| RECIPIENTS RECEIVING CUSTODIAL CARE ARE NO LONGER |
| CAPABLE OF SELF- PRESERVATION THEN THE OCCUPANCY |
| CHANGES TO AN I-2 OCCUPANCY. |
| |
| PLEASE NOTE THE BACK UNIT BEING UNDER A SEPARATE PERMIT |
| DOES NOT MEAN THAT THE AMOUNT OF OCCUPANTS FOR THIS |
| FACILITY ARE NOT COMBINED!!! SHEET S-11 DOES NOT SHOW |
| THE USAGE OF THE ROOMS NOR THE AMOUNT OF OCCUPANTS THAT |
| WILL BE SHARING SLEEPING QUARTERS. PLEASE NOTE THAT |
| THIS MAY CREATE A CHANGE OF OCCUPANCY FROM THE R2 |
| APARTMENTS TO A I-1 OCCUPANCY. SEE 2014 FBC-B 308.3 |
| 308.3 INSTITUTIONAL GROUP I-1. UNDER THE 2012 IBC-B |
| BASE CODE THE COMMENTARY ALSO USES THE TERMINOLOGY |
| FACILITY. THE NUMBER OF PEOPLE RECEIVING CARE IN THE |
| FACILITY. NOTE STATE LICENSING WILL BE FOR THE |
| FACILITY, THE OCCUPATIONAL LICENSE/ BUSINESS TAX IS |
| LICENSED FOR THE FACILITY. |
| |
| THIS OCCUPANCY SHALL INCLUDE BUILDINGS, STRUCTURES OR |
| PORTIONS THEREOF FOR MORE THAN 16 PERSONS WHO RESIDE ON |
| A 24 HOUR BASIS IN A SUPERVISED ENVIRONMENT AND RECEIVE |
| CUSTODIAL CARE. THE PERSONS RECEIVING CARE ARE CAPABLE |
| OF SELF PRESERVATION. THIS GROUP SHALL INCLUDE, BUT NOT |
| BE LIMITED TO, THE FOLLOWING: |
| ALCOHOL AND DRUG CENTERS, ASSISTED LIVING FACILITIES, |
| CONGREGATE CARE FACILITIES, CONVALESCENT FACILITIES, |
| GROUP HOMES, HALFWAY HOUSES, RESIDENTIAL BOARD AND |
| CUSTODIAL CARE FACILITIES AND OR SOCIAL REHABILITATION |
| FACILITIES. |
| |
| 2) SHEET S-4 & S11 PLEASE SHOW RATED WALLS BETWEEN |
| SLEEPING ROOMS. 2014 FBC-B 420.2 SEPARATION WALLS. |
| WALLS SEPARATING DWELLING UNITS IN THE SAME BUILDING, |
| WALLS SEPARATING SLEEPING UNITS IN THE SAME BUILDING |
| AND WALLS SEPARATING DWELLING OR SLEEPING UNITS FROM |
| OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME |
| BUILDING SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN |
| ACCORDANCE WITH SECTION 708. |
| PLEASE NOTE THAT WE ARE REVIEWING THE SLEEPING ROOMS AS |
| DORMS AS DEFINED UNDER THE FBC-B DORMITORY. A SPACE IN |
| A BUILDING WHERE GROUP SLEEPING ACCOMMODATIONS ARE |
| PROVIDED IN ONE ROOM, OR IN A SERIES OF CLOSELY |
| ASSOCIATED ROOMS, FOR PERSONS NOT MEMBERS OF THE SAME |
| FAMILY GROUP, UNDER JOINT OCCUPANCY AND SINGLE |
| MANAGEMENT, AS IN COLLEGE DORMITORIES OR FRATERNITY |
| HOUSES. |
| UNDER THE CITY MUNI-CODE ONLY TWO PEOPLE CAN USE A |
| DWELLING UNIT WHO ARE NOT RELATED SEE THE TERM FAMILY |
| 18-92. THE TERM FAMILY SHALL NOT INCLUDE THE OCCUPANTS |
| OF GROUP HOMES, CONGREGATE LIVING FACILITIES OR OTHER |
| SIMILAR USE WITH SHARED COOKING OR SANITARY FACILITIES. |
| |
| 3) PLEASE PROVIDE A LIFE SAFETY PLAN THAT SHOWS, SITE |
| PLAN, THE FIRE RATING OF SLEEPING ROOMS, THE MEANS OF |
| EGRESS FOR EACH SLEEPING ROOM TO THE PUBLIC WAY, AN |
| ACCESSIBLE MEANS OF EGRESS TO THE PUBLIC WAY, |
| ACCESSIBLE PARKING, COMMON PATH OF TRAVEL, THE SIZE OF |
| THE EMERGENCY ACCESS WINDOWS (VENT) FOR EACH SLEEPING |
| ROOM, FIRE RATING OF STAIRS, FIRE RATING OF SLEEPING |
| ROOM DOORS, EXIT SIGNS, EMERGENCY LIGHTING OF |
| CORRIDORS, STAIRS. 107.3.5.1.1 MINIMUM PLAN REVIEW |
| CRITERIA FOR COMMERCIAL BUILDINGS. |
| |
| 4) PLANS WILL NEED TO SHOW COMPLIANCE WITH: 2014 FBC-B |
| 420.3 HORIZONTAL SEPARATION. |
| FLOOR ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME |
| BUILDINGS, FLOOR ASSEMBLIES SEPARATING SLEEPING UNITS |
| IN THE SAME BUILDING AND FLOOR ASSEMBLIES SEPARATING |
| DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES |
| CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE |
| CONSTRUCTED AS HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH |
| SECTION 711. A 2 HOUR FIRE FLOOR/ CEILING ASSEMBLY WILL |
| BE REQUIRED. |
| |
| 5A) PLANS WILL NEED TO SHOW COMPLIANCE WITH: 2014 FBC-B |
| 420.4 AUTOMATIC SPRINKLER SYSTEM. GROUP R OCCUPANCIES |
| SHALL BE EQUIPPED THROUGHOUT WITH AN AUTOMATIC |
| SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.2.8. |
| GROUP I-1 OCCUPANCIES SHALL BE EQUIPPED THROUGHOUT WITH |
| AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| SECTION 903.2.6. QUICK RESPONSE OR RESIDENTIAL |
| AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN ACCORDANCE |
| WITH SECTION 903.3.2. |
| |
| 5B) PLEASE NOTE THAT IF A NFPA R13 FIRE SPRINKLER IS |
| PROPOSED IN THE 3 STORY STRUCTURE NO STORY INCREASE CAN |
| BE TAKEN, A FULL NFPA 13 FIRE SPRINKLER YOU CAN TAKE A |
| 1 STORY INCREASE SEE FBC-B TABLE 503 ONLY ALLOWS 2 |
| STORIES FOR A BUILDING TYPE VB FOR A R4 OR I1 |
| OCCUPANCIES NO SPRINKLERS!!!!!!!! |
| |
| 6) PLANS WILL NEED TO SHOW COMPLIANCE WITH: 2014 FBC-B |
| 420.5 SMOKE DETECTION AND FIRE ALARM SYSTEMS. |
| FIRE ALARM SYSTEMS AND SMOKE ALARMS SHALL BE PROVIDED |
| IN GROUP I-1, R-1 AND R-2 OCCUPANCIES IN ACCORDANCE |
| WITH SECTIONS 907.2.6, 907.2.8 AND 907.2.9, |
| RESPECTIVELY. SINGLE-OR MULTIPLE-STATION SMOKE ALARMS |
| SHALL BE IN ACCORDANCE WITH SECTION 907.2.11. |
| |
| 7) 2014 FBC-EXISTING BUILDING CODE 1006.1 ACCESSIBILITY |
| IN PORTIONS OF BUILDINGS UNDERGOING A CHANGE OF |
| OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE |
| PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY. |
| |
| PLEASE NOTE IF THIS FACILITY IS EITHER A R4 OR AN I1 |
| OCCUPANCY, IN EITHER CASE THE COMMON AREAS WILL NEED TO |
| COMPLY WITH THE FLORIDA ACCESSIBILITY CODE AND |
| DEPENDING ON THE AMOUNT OF UNITS, COMPLY WITH THE |
| REQUIREMENTS OF 224.2, TABLE 224.2, 224.4 , TABLE |
| 224.4. |
| |
| 8) NONE OF THE PLANS SHOW THE WIND DESIGN CRITERIA NOR |
| PRESSURES FOR COMPONENTS & CLADDING. |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 8.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 8.2. RISK CATEGORY. |
| |
| 8.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| |
| 8.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 8.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. |
| |
| 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 9) / 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 10) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 11) SHEET S-4, NOTE PN-6. PLEASE BE AWARE FLOORING |
| TYPES NOT PICKED. FOR TILE, STONE, MARBLE AND WOOD |
| FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT |
| TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND |
| MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE |
| STANDARDS. PLEASE PROVIDE TEST REPORTS SHOWING |
| COMPLIANCE WITH: |
| |
| 11A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 11B) FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 11C) TYPE III-TYPE V CONSTRUCTION: FBC-B-2014 720.2 |
| CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE |
| CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF |
| CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT |
| MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE |
| THAN 450. |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |