2016-07-28 09:35:241254 PALM BEACH LAKES BOULEVARD
 PERMIT #16071041
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 NO AGE GROUPS, NUMBER OF CLIENTS OR NUMBER OF STAFF
 PROVIDED. PER SECTION 16.7.5 DAY-CARE STAFF. ADEQUATE
 ADULT STAFF SHALL BE ON DUTY IN THE FACILITY AND ALERT
 AT ALL TIMES WHERE CLIENTS ARE PRESENT.
  
 PER SECTION 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM
 DOOR LOCK SHALL BE DESIGNED TO ALLOW OPENING OF THE
 LOCKED DOOR FROM THE OUTSIDE BY AN OPENING DEVICE THAT
 SHALL BE READILY ACCESSIBLE TO THE STAFF.
  
 PER SECTION 16.7.3 INSPECTIONS. FIRE PREVENTION
 INSPECTIONS SHALL BE CONDUCTED MONTHLY BY A TRAINED
 SENIOR MEMBER OF THE STAFF, AFTER WHICH A COPY OF THE
 LATEST INSPECTION REPORT SHALL BE POSTED IN A
 CONSPICUOUS PLACE IN THE DAY-CARE FACILITY.
  
 PER SECTION 16.7.3.3 IT SHALL BE THE DUTY OF SITE
 ADMINISTRATORS AND STAFF MEMBERS TO INSPECT ALL EXIT
 FACILITIES DAILY TO ENSURE THAT ALL STAIRWAYS, DOORS,
 AND OTHER EXITS ARE IN PROPER CONDITION.
  
 THE TWO BATHROOM DOORS OBSTRUCT EGRESS. DURING ITS
 SWING, ANY DOOR IN A MEANS OF EGRESS SHALL LEAVE NOT
 LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF AN AISLE,
 CORRIDOR, HALLWAY OR LANDING UNOBSTRUCTED AND SHALL
 PROJECT NOT MORE THAN 7-INCHES INTO THE REQUIRED WIDTH
 OF THE EGRESS PATH WHEN FULLY OPEN.
  
 NO EMERGENCY LIGHTING PROVIDED.
  
 REAR EXIT LEADS TO A FENCED ENCLOSURE. FENCED
 PLAYGROUND AREA SHALL BE PROVIDED WITH TWO SEPARATED
 EXITS. NO DETAILS OF PLAYGROUND AREA SUBMITTED.
  
 PLANS DO NOT INDICATE A FIRE RATING BETWEEN THE
 DAY-CARE OCCUPANCY AND THE NEIGHBORING TENTANTS PER
 TABLE 6.1.14.4.1(A).
  
 WILL THE DAY-CARE BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM OR A FIRE ALARM SYSTEM?
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  