2016-07-28 12:21:30ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB NAME: BRIGHT FROM THE START CHILD CARE
 JOB ADDRESS: 1254 PALM BEACH LAKES BLVD.
 DESCRIPTION: CHANGE OF OCCUPANCY FROM RETAIL TO CHILD
 DAYCARE
 MAST. PERMIT: 16071041
 REVISION:
  
 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE
 THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE,
 THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND
 SIGNATURE SHALL APPEAR ON ALL DOCUMENTS).
 2. FOR PROPER DETERMINATION OF MINIMUM REQUIREMENTS,
 THE NUMBER OF BEDS (CHILD COUNT) ACCEPTED AT ONE TIME
 AND THE AGE GROUPS.
 3. AS PART OF THE REQUIRED DRAWINGS, YOU SHALL PROVIDE
 ELECTRICAL SHEETS AS INDICATED IN THE FBC-B 107.3.5
 ELECTRICAL. INCLUDE THE LOCATION OF EVERY ELECTRICAL
 OUTLET, LUMINAIRE AND ITS RESPECTIVE SWITCH. THE
 LOCATION OF THE ELECTRICAL PANEL SHALL BE SO INDICATED
 AS WELL.
 4. THE LIGHTING SHALL COMPLY WITH THE REQUIREMENTS OF
 THE FBC-ENERGY CONSERVATION.
 5. NEC 215.5: ELECTRICAL RISER DIAGRAM WITH LOAD CALCS.
 6. NEC 408.4: PANEL SCHEDULE
 7. THE ABOVE IS NOT A COMPREHENSIVE LIST OF ALL THE
 ELECTRICAL SUBMITTAL REQUIREMENTS. THE ASSISTANCE OF A
 DESIGN PROFESSIONAL WILL FACILITATE THE SUBMITTAL.
 8. FIRE ALARM SHALL BE PROVIDED UNDER A SEPARATE PERMIT
 AND SUBMITTAL PACKAGE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER